Drive parameters will apply to the settings when the drive is running during MEMOBUS/Modbus communications. This section gives information about the available functions and their related parameters.
Executable Functions
A PLC can do these operations with MEMOBUS/Modbus communications. Parameter settings (except H5-xx) do not have an effect on the availability of these operations.
Drive Control
Select the external command that sets the frequency references and motor run/stop with MEMOBUS/Modbus communications. Use the information in Table 1 to set the parameters as specified by the application.
Table 1. Necessary Parameter Settings for Drive Control from MEMOBUS/Modbus
|
LOCAL Control Selected
|
No.
|
Name
|
Setting Value
|
|
External reference 1
|
b1-01
|
Frequency Reference Selection 1
|
2 [Memobus/Modbus Communications]
|
|
b1-02
|
Run Command Selection 1
|
2 [Memobus/Modbus Communications]
|
|
External reference 2
|
b1-15
|
Frequency Reference Selection 2
|
2 [Memobus/Modbus Communications]
|
|
b1-16
|
Run Command Selection 2
|
2 [Memobus/Modbus Communications]
|
For more information about operation mode selection, refer to [Frequency Reference Selection 1] and b1-02 [Run Command Selection 1]. Refer to H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection] for more information about external commands.