When the drive is operating or is prepared to accept a Run command, the MFDO terminal to which Drive Ready [H2-xx = 6] is set will enter the ON status.

In these conditions, Drive Ready is OFF and the drive ignores Run commands:

  • The drive is de-energized

  • During a fault

  • There is problem with the control power supply

  • There is a parameter setting error that will not let the drive run, although a Run command is entered

  • An overvoltage or undervoltage fault occurs when the Run command is entered

  • The drive is in Programming Mode.