oL1
|
Motor Overload
|
The load is too heavy.
|
Decrease the load.
Note:
Reset oL1 when U4-16 [Motor oL1 Level] < 100.
|
|
The acceleration/deceleration times or cycle times are too short.
|
|
|
Overload occurred while running at low speed.
|
-
Decrease the load when running at low speed.
-
Increase the motor speed.
-
If the motor is run frequently at low speeds, replace the motor with a larger motor or use a drive-dedicated motor.
Note:
For general-purpose motors, overload can occur while running at low speed when operating at below the rated current.
|
|
L1-01 [Motor Overload (oL1) Protection] is set incorrectly.
|
Set L1-01 in as specified by the motor qualities for a drive-dedicated motor.
|
|
The V/f pattern does not fit the motor qualities.
|
-
Examine the ratios between the V/f pattern frequency and voltage. Decrease the voltage if it is too high compared to the frequency.
-
Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2, adjust E3-04 to E3-10. Decrease the values set in E1-08 [Mid Point A Voltage] and E1-10 [Minimum Output Voltage].
Note:
If the values set in E1-08 and E1-10 are too low, the overload tolerance will decrease at low speeds.
|
|
E1-06 [Base Frequency] is set incorrectly.
|
Set E1-06 to the rated frequency shown on the motor nameplate.
|
|
One drive is operating more than one motor.
|
Set L1-01 = 0 [Motor Overload (oL1) Protection = Disabled], connect thermal overload relay to each motor to prevent damage to the motor.
|
|
The electronic thermal protector qualities and the motor overload properties do not align.
|
|
|
The electronic thermal protector is operating at an incorrect level.
|
Set E2-01 [Motor Rated Current (FLA)] correctly to the value specified by the motor nameplate.
|
|
There is increased motor loss from overexcitation operation.
|
-
Lower the value set in n3-13 [OverexcitationBraking (OEB) Gain].
-
Set L3-04 ≠ 4 [Stall Prevention during Decel ≠ Overexcitation/High Flux].
-
Set n3-23 = 0 [Overexcitation Braking Operation = Disabled].
|
|
The speed search-related parameters are set incorrectly.
|
-
Examine the settings for all speed search related parameters.
-
Adjust b3-03 [Speed Search Deceleration Time].
-
Set b3-24 = 1 [Speed Search Method Selection = Speed Estimation] after Auto-Tuning.
|
|
Phase loss in the input power supply is causing the output current to change.
|
Make sure that there is no phase loss, and repair problems.
|
|
Overload occurred during overexcitation deceleration.
|
|
Note:
-
The drive detects this fault if the electronic thermal protector of the drive started the motor overload protection.
-
Do a Fault Reset to clear the fault.
-
L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
|