No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-01

(3130)

EZ Tuning Mode Selection

Sets the type of Auto-Tuning for EZOLV control.

0
Motor Parameter Setting
 
1
Line-to-Line Resistance
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-02

(3131)

Motor Type Selection

Sets the type of motor.

0
Induction (IM)
 
1
Permanent Magnet (PM)
 
2
Synchronous Reluctance (SynRM)
 

0

(0, 1, 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-04

(3133)

Motor Rated Revolutions

Sets rated rotation speed (min-1) of the motor.

-

((40 Hz to 120 Hz) × 60 × 2/E9-08)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-05

(3134)

Motor Rated Frequency

Sets the rated frequency (Hz) of the motor.

Determined by E9-01 and o2-04

(40.0 - 120.0 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-06

(3135)

Motor Rated Voltage

Sets the rated voltage (V) of the motor.

200 V Class: 200.0 V,

400 V Class: 400.0 V

(200 V Class: 0.0 - 255.0 V, 400 V Class: 0.0 - 510.0 V)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-07

(3136)

Motor Rated Current

Sets the rated current (A) of the motor.

Determined by o2-04, C6-01

(10% to 200% of the drive rated current)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-08

(3137)

PM Motor Rated Power

Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].

Note:

On drive models 2xxx, and 4002 to 4675, the setting unit is 0.01 kW. The setting range is 0.10 kW to 650.00 kW (0.10 HP to 650.00 HP).

On drive models 4810 to 4H12, the setting unit is 0.1 kW. The setting range is 0.1 kW to 1000.0 kW (0.1 HP to 1340.5 HP).

Determined by E9-10

(0.10 - 1000.0)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

T4-09

(3138)

Number of Poles

Sets the number of motor poles.

Determined by E9-01

(2 - 120)

Details