bUS
|
Option Communication Error
|
The drive did not receive a signal from the controller.
|
Correct wiring errors.
|
|
The communications cable wiring is incorrect.
|
|
There is a short-circuit in the communications cable or the communications cable is not connected.
|
|
|
Electrical interference caused a communication data error.
|
-
Examine the control circuit lines, main circuit lines, and ground wiring, and decrease the effects of electrical interference.
-
Make sure that a magnetic contactor is not the source of the electrical interference, then use a Surge Protective Device if necessary.
-
Use only the recommended cables or other shielded line. Ground the shield on the controller side or the drive input power side.
-
Separate the communication wiring from drive power lines, and install a noise filter to the input side of the power supply for communication.
-
Decrease the effects of electrical interference from the controller.
|
|
The option is incorrectly installed to the drive.
|
Correctly install the option to the drive.
|
|
The option is damaged.
|
If the fault continues and the wiring is correct, replace the option.
|
Note:
-
The drive detects this error if the Run command or frequency reference is assigned to the option card.
-
Do a Fault Reset to clear the fault.
-
If the drive detects this error, the drive will operate the motor as specified by the stopping method set in F6-01 [Communication Error Selection].
|