Parameters that Change from the Default Settings with E3-01 [Motor 2 Control Mode Selection]

The values for the parameters in these tables depend on the values for parameter E3-01. When you change the setting for E3-01, the default settings will change.

 

No.

Name

Range

Unit

Motor 2 Control Method (setting value of E3-01)

V/f

(0)

CL-V/f

(1)

OLV

(2)

CLV

(3)

C3-21

Motor 2 Slip Compensation Gain

0.0 - 2.50

0.1

0.0

-

1.0

1.0

C3-22

Motor 2 Slip Comp Delay Time

0 - 10000

1 ms

2000

-

200

-

C5-21

Motor 2 ASR Proportional Gain 1 (P)

0.00 - 300.00

0.01

-

0.20

-

20.00

C5-22

Motor 2 ASR Integral Time 1 (I)

0.000 - 10.000

0.001 s

-

0.200

-

0.500

C5-23

Motor 2 ASR Proportional Gain 2 (P)

0.00 - 300.00

0.01

-

0.02

-

20.00

C5-24

Motor 2 ASR Integral Time 2 (I)

0.000 - 10.000

0.001 s

-

0.050

-

0.500

C5-26

Motor 2 ASR Delay Time

0.000 - 0.500

0.001 s

-

-

-

0.004

E3-04

Motor 2 Maximum Output Frequency

40.0 - 590.0

0.1 Hz

60.0

60.0

60.0

60.0

E3-05

Motor 2 Maximum Output Voltage

0.0 - 255.0

1

0.1 V

200.0

200.0

200.0

200.0

E3-06

Motor 2 Base Frequency

0.0 - 590.0

0.1 Hz

60.0

60.0

60.0

60.0

E3-07

Motor 2 Mid Point A Frequency

0.0 - 590.0

0.1 Hz

3.0

3.0

3.0

-

E3-08

Motor 2 Mid Point A Voltage

0.0 - 255.0

1

0.1 V

15.0

15.0

11.0

-

E3-09

Motor 2 Minimum Output Frequency

0.0 - 590.0

0.1 Hz

1.5

1.5

0.5

0.0

E3-10

Motor 2 Minimum Output Voltage

0.0 - 255.0

1

0.1 V

9.0

9.0

2.0

-

E3-11

Motor 2 Mid Point B Frequency

0.0 - 590.0

Determined by o1-04

0.0

0.0

0.0

0.0

E3-12

Motor 2 Mid Point B Voltage

0.0 - 255.0

1

0.1 V

0.0

0.0

0.0

0.0

E3-13

Motor 2 Base Voltage

0.0 - 255.0

1

0.1 V

0.0

0.0

0.0

0.0

 
1

This is the value for 200 V class drives. Double the value for 400 V class drives.