This procedure will show all parameters that are not at their default values. This is very useful when you replace a drive. This lets you quickly access and re-edit changed parameters. When all parameters are at their default values, the keypad will show “0 Parameters”.

  1. Push [F2 Key] (Home) to show the HOME screen.
    Note:
    • When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.

    • If [Home] is not shown on [F2 Key], push [F1 Key] (Back) to show [Home] on [F2 Key].

  2. Push [F2 Key] (Menu).
  3. Push [Up arrow key] or [Down arrow key] to select [Modified Param / Fault Log], then push [ENTER Key].
  4. Push [Up arrow key] or [Down arrow key] to select [Modified Parameters], then push [ENTER Key].
  5. Push [ENTER Key].
  6. Push [Up arrow key] or [Down arrow key] to show the parameter to examine.
  7. To re-edit a parameter, push [Up arrow key] or [Down arrow key], select the parameter to edit, then push [ENTER Key].
  8. Push [LEFT Key] or [RIGHT Key] to select the digit, then push [Up arrow key] or [Down arrow key] to change the value.
  9. When you are done changing the value, push [ENTER Key].

The parameter revision procedure is complete.