U2: Fault Trace

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-01

(0080)

Current Fault

Shows the fault that the drive has when viewing the monitor.

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-02

(0081)

Previous Fault

Shows the fault that occurred most recently.

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-03

(0082)

Freq Reference@Fault

Shows the frequency reference at the fault that occurred most recently.

Use U1-01 [Frequency Reference] to monitor the frequency reference value.

0.01 Hz

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-04

(0083)

Output Freq @ Fault

Shows the output frequency at the fault that occurred most recently.

Use U1-02 [Output Frequency] to monitor the actual output frequency.

0.01 Hz

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-05

(0084)

Output Current@Fault

Shows the output current at the fault that occurred most recently.

Use U1-03 [Output Current] to monitor the output current. The keypad shows the value of U1-03 in amperes (A).

When you use MEMOBUS/Modbus communications to show the monitor, the current is “8192 = drive rated current (A)”. Use the formula: “Numerals being displayed / 8192 × drive rated current (A)” to use the MEMOBUS/Modbus communication current value shown in the monitor.

When the drive model changes, the display units for this parameter also change.

  • 0.01 A: 2004 - 2042, 4002 - 4023

  • 0.1 A: 2056 - 2415, 4031 - 4675

  • 1 A: 4810 - 4H12

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-06

(0085)

Motor Speed @ Fault

Shows the motor speed at the fault that occurred most recently.

Use U1-05 [Motor Speed] to monitor the motor speed.

0.01 Hz

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-07

(0086)

Output Voltage@Fault

Shows the output voltage reference at the fault that occurred most recently.

Use U1-06 [Output Voltage Ref] to monitor the output voltage reference.

0.1 V

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-08

(0087)

DC Bus Voltage@Fault

Shows the DC bus voltage at the fault that occurred most recently.

Use U1-07 [DC Bus Voltage] to monitor the DC bus voltage.

1 V

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-09

(0088)

Output Power @ Fault

Shows the output power at the fault that occurred most recently.

Use U1-08 [Output Power] to monitor the output power.

0.1 kW

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-10

(0089)

Torque Ref @ Fault

Shows the torque reference at the fault that occurred most recently as a percentage of the motor rated torque.

Use U1-09 [Torque Reference] to monitor the torque reference.

0.1%

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-11

(008A)

Input Terminal Status @ Fault

Shows the status of the MFDI terminals at the most recent fault where 1 = (ON) and 0 = (OFF).

For example, U2-11 shows “00000011” when terminals S1 and S2 are ON.

Use U1-10 [Input Terminal Status] to monitor the MFDI terminal status.

bit0
Terminal S1

Shows the status of MFDI terminal S1.

bit1
Terminal S2

Shows the status of MFDI terminal S2.

bit2
Terminal S3

Shows the status of MFDI terminal S3.

bit3
Terminal S4

Shows the status of MFDI terminal S4.

bit4
Terminal S5

Shows the status of MFDI terminal S5.

bit5
Terminal S6

Shows the status of MFDI terminal S6.

bit6
Terminal S7

Shows the status of MFDI terminal S7.

bit7
Terminal S8

Shows the status of MFDI terminal S8.

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-12

(008B)

Output Terminal Status @ Fault

Shows the status of the MFDO terminals at the most recent fault where 1 = (ON) and 0 = (OFF).

For example, U2-12 shows “00000011” when terminals M1 and M3 are ON.

Use U1-11 [Output Terminal Status] to monitor the MFDO terminal status.

bit0
Terminal M1-M2

Shows the status of MFDO terminals M1-M2.

bit1
Terminal M3-M4

Shows the status of MFDO terminals M3-M4.

bit2
Terminal P1-C1

Shows the status of multi-function photocoupler output terminals P1-C1.

bit3
Terminal P2-C2

Shows the status of multi-function photocoupler output terminals P2-C2.

bit4
Not used (normal value of 0).
 
bit5
Not used (normal value of 0).
 
bit6
Not used (normal value of 0).
 
bit7
Fault relay MA/MB-MC

Displays the status of fault relay output terminals MA/MB-MC.

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-13

(008C)

Operation Status @ Fault

Shows the status of the MFDO terminals at the most recent fault where 1 = (ON) and 0 = (OFF).

For example, U2-13 shows “00000001” during run.

Use U1-12 [Drive Status] to monitor the MFDO terminal status.

bit0
During Run
 
bit1
During zero-speed
 
bit2
During reverse
 
bit3
During fault reset signal input
 
bit4
During speed agreement
 
bit5
Drive ready
 
bit6
During minor fault detection
 
bit7
During fault detection
 

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-14

(008D)

Elapsed Time @ Fault

Shows the cumulative operation time of the drive at the fault that occurred most recently.

Use U4-01 [Cumulative Ope Time] to monitor the cumulative operation time.

1 h

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-15

(07E0)

SFS Output @ Fault

Shows the output frequency after soft start at the fault that occurred most recently.

Use U1-16 [SFS Output Frequency] to monitor the output frequency after soft start.

0.01 Hz

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-16

(07E1)

q-Axis Current@Fault

Shows the q-Axis current of the motor at the fault that occurred most recently.

Use U6-01 [Iq Secondary Current] to monitor the q-Axis current of the motor.

0.1 %

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-17

(07E2)

d-Axis Current@Fault

Shows the d-Axis current of the motor at the fault that occurred most recently.

Use U6-02 [Id ExcitationCurrent] to monitor the d-Axis current of the motor.

0.1%

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-19

(07E4)

ControlDeviation@Flt

Shows the amount of control axis deviation (Δθ) at the fault that occurred most recently.

Use U6-10 [ContAxisDeviation Δθ] to monitor the actual amount of control axis deviation (Δθ).

0.1 °

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-20

(008E)

Heatsink Temp @Fault

Shows the heatsink temperature at the fault that occurred most recently.

Use U4-08 [Heatsink Temperature] to monitor the temperature of the heatsink.

1 °C

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-21

(1166)

Expert

STPo Detect @ Fault

Monitors conditions to detect STPo [Motor Step-Out Detected] faults. The bit for each condition is shown as ON or OFF.

bit0
Excessive current
 
bit1
Induced voltage deviation
 
bit2
d-axis current deviation
 
bit3
Motor lock at startup
 
bit4
Acceleration stall continue
 
bit5
Acceleration stall repeat
 
bit6
Not used (normal value of 0).
 
bit7
Not used (normal value of 0).
 

No signal output available

No.

(Hex.)

Name

Description

MFAO Signal Level

U2-27

(07FA)

Expert

Motor Temp @ Fault

Shows the motor temperature detected by the NTC thermistor when there is a fault. When H3-xx ≠ 17 [Terminal A1 to A3 Signal Level Select ≠ Motor Temperature (NTC Input)] , or L1-15 = 0 [Motor 1 NTC Thermistor Select = Disabled] and L1-17 = 0 [Motor 2 NTC Thermistor Select = Disabled] the drive shows 20 °C. The drive shows negative temperatures as 0 °C.

No signal output available