No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L5-01

(049E)

Number of Auto-Restart Attempts

Sets the number of times that the drive will try to restart.

0

(0 - 10 times)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L5-02

(049F)

Fault Contact at Restart Select

Sets the function that sends signals to the MFDO terminal set for Fault [H2-xx = E] while the drive is automatically restarting.

0
Active Only when Not Restarting
 
1
Always Active
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L5-03

(04A0)

Continuous Method Max Restart T

Sets the time for which the drive will try to restart. If the drive cannot restart inthe time set in L5-03, the drive detects a fault. This is available when L5-05 = 0 [Auto-Restart Method = Continuous/Immediate Attempts].

10.0 s

(0.5 - 180.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L5-04

(046C)

Interval Method Restart Time

Sets the time interval between each Auto Restart attempt. This function is enabled when L5-05 = 1 [Auto Restart Operation Selection = Use L5-04 Time].

10.0 s

(0.5 - 600.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L5-05

(0467)

Auto-Restart Method

Sets the count method for the Auto Restart operation.

0
Continuous/Immediate Attempts
 
1
Interval/Attempt after L5-04 sec
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L5-07

(0B2A)

Fault Reset Enable Select Grp1

Use these 4 digits to set the Auto Restart function for oL1 to oL4. From left to right, the digits set oL1, oL2, oL3, and oL4, in order.

0000
Disabled
 
0001
Enabled (—/—/—/oL4)
 
0010
Enabled (—/—/oL3/—)
 
0011
Enabled (—/—/oL3/oL4)
 
0100
Enabled (—/oL2/—/—)
 
0101
Enabled (—/oL2/—/oL4)
 
0110
Enabled (—/oL2/oL3/—)
 
0111
Enabled (—/oL2/oL3/oL4)
 
1000
Enabled (oL1/—/—/—)
 
1001
Enabled (oL1/—/—/oL4)
 
1010
Enabled (oL1/—/oL3/—)
 
1011
Enabled (oL1/—/oL3/oL4)
 
1100
Enabled (oL1/oL2/—/—)
 
1101
Enabled (oL1/oL2/—/oL4)
 
1110
Enabled (oL1/oL2/oL3/—)
 
1111
Enabled (oL1/oL2/oL3/oL4)
 

1111

(0000 - 1111)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

L5-08

(0B2B)

Fault Reset Enable Select Grp2

Use these 4 digits to set the Auto Restart function for Uv1, ov, oH1, and GF. From left to right, the digits set Uv1, ov, oH1, and GF, in order.

0000
Disabled
 
0001
Enabled (—/–/—/GF)
 
0010
Enabled (—/–/oH1/–)
 
0011
Enabled (—/–/oH1/GF)
 
0100
Enabled (—/ov/—/–)
 
0101
Enabled (—/ov/—/GF)
 
0110
Enabled (—/ov/oH1/–)
 
0111
Enabled (—/ov/oH1/GF)
 
1000
Enabled (Uv1/–/—/–)
 
1001
Enabled (Uv1/–/—/GF)
 
1010
Enabled (Uv1/–/oH1/–)
 
1011
Enabled (Uv1/–/oH1/GF)
 
1100
Enabled (Uv1/ov/—/–)
 
1101
Enabled (Uv1/ov/—/GF)
 
1110
Enabled (Uv1/ov/oH1/–)
 
1111
Enabled (Uv1/ov/oH1/GF)
 

1111

(0000 - 1111)

Details