Jump to main content

H2: Multi-function Digital Output

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-01

(040B)

Term M1-M2 Function Selection

Sets the function for MFDO terminal M1-M2.

Note:

When you do not use the terminal or when you use the terminal in through mode, set this parameter to F.

0

(0 - 1FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-02

(040C)

Term M3-M4 Function Selection

Sets the function for MFDO terminal M3-M4.

Note:

When you do not use the terminal or when you use the terminal in through mode, set this parameter to F.

1

(0 - 1FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-03

(040D)

Term M5-M6 Function Selection / Term P1-C1 Function Selection

Sets the function for MFDO terminal M5-M6 or P1-C1.

Note:
  • When you use a drive with a relay output/screw clamp terminal board type control circuit board (GA70xxxxxxxxxx-A models), H2-03 sets MFDO terminal M5-M6.

  • When you use a drive with a photocoupler output/screw clamp terminal board type control circuit board (GA70xxxxxxxxxx-C models), H2-03 sets MFDO terminal P1-C1.

  • When you do not use the terminal or when you use the terminal in through mode, set this parameter to F.

2

(0 - 1FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-04

(040E)

Term P2-C2 Function Selection

Sets the function for MFDO terminal P2-C2.

Note:

When you do not use the terminal or when you use the terminal in through mode, set this parameter to F.

F

(0 - 1FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-06

(0437)

Watt Hour Output Unit Selection

Sets the unit for the output signal when H2-01 to H2-04 = 39 [MFDO Function Selection = Watt Hour Pulse Output].

0
0.1 kWh units
 
1
1 kWh units
 
2
10 kWh units
 
3
100 kWh units
 
4
1000 kWh units
 

0

(0 - 4)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-07

(0B3A)

Modbus Register 1 Address Select

Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.

0001

(0001 - 1FFF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-08

(0B3B)

Modbus Register 1 Bit Select

Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.

0000

(0000 - FFFF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-09

(0B3C)

Modbus Register 2 Address Select

Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.

0001

(0001 - 1FFF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-10

(0B3D)

Modbus Register 2 Bit Select

Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.

0000

(0000 - FFFF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-20

(1540)

Comparator 1 Monitor Selection

Sets the monitor number (Ux-xx) for comparator 1.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set H2-20 = 102 to monitor U1-02 [Output Frequency].

When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set H2-20 = 1301 to monitor Ud-01.

102

(000 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-21

(1541)

Comparator 1 Lower Limit

Sets the lower limit detection level for comparator 1 when the full scale analog output for the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.

0.0%

(0.0 - 300.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-22

(1542)

Comparator 1 Upper Limit

Sets the upper limit detection level for comparator 1 when the full scale analog output for the monitor selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.

0.0%

(0.0 - 300.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-23

(1543)

Comparator 1 Hysteresis

Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the monitor selected in H2-20 [Comparator 1 Monitor Selection].

0.0%

(0.0 - 10.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-24

(1544)

Comparator 1 On-Delay Time

Sets the on-delay time for comparator 1.

0.0 s

(0.0 - 600.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-25

(1545)

Comparator 1 Off-Delay Time

Sets the off-delay time for comparator 1.

0.0 s

(0.0 - 600.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-26

(1546)

Comparator 2 Monitor Selection

Sets the monitor number (Ux-xx) for comparator 2.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set H2-26 = 103 to monitor U1-03 [Output Current].

When the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set H2-26 = 1301 to monitor Ud-01.

103

(000 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-27

(1547)

Comparator 2 Lower Limit

Sets the lower limit detection level for comparator 2 as a percentage of the full scale analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].

0.0%

(0.0 - 300.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-28

(1548)

Comparator 2 Upper Limit

Sets the upper limit detection level for comparator 2 as a percentage of the full scale analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].

0.0%

(0.0 - 300.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-29

(1549)

Comparator 2 Hysteresis

Sets the hysteresis level for comparator 2 as a percentage of the full scale analog output for the monitor selected in H2-26 [Comparator 2 Monitor Selection].

0.0%

(0.0 - 10.0%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-30

(154A)

Comparator 2 On-Delay Time

Sets the on-delay time for comparator 2.

0.0 s

(0.0 - 600.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-31

(154B)

Comparator 2 Off-Delay Time

Sets the off-delay time for comparator 2.

0.0 s

(0.0 - 600.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-32

(159A)

Comparator 1 Filter Time

Sets the time constant that is applied to the primary delay filter used for the analog output of the monitor selected with H2-20 [Comparator 1 Monitor Selection].

0.0s

(0.0 - 10.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-33

(159B)

Comparator1 Protection Selection

Sets drive operation when it detects CP1 [Comparator1 Limit Fault].

0
Ramp to Stop
 
1
Coast to Stop
 
2
Fast Stop (Use C1-09)
 
3
Alarm Only
 
4
Digital Output Only
 

4

(0 - 4)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-34

(159C)

Comparator 2 Filter Time

Sets the time constant that is applied to the primary delay filter used for the analog output of the monitor selected with H2-26 [Comparator 2 Monitor Selection].

0.0s

(0.0 - 10.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-35

(159D)

Comparator2 Protection Selection

Sets drive operation when it detects CP2 [Comparator2 Limit Fault].

0
Ramp to Stop
 
1
Coast to Stop
 
2
Fast Stop (Use C1-09)
 
3
Alarm Only
 
4
Digital Output Only
 

4

(0 - 4)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-36

(159E)

Comparator 1 Ineffective Time

Sets the length of time that CP1 [Comparator1 Limit Fault] is disabled.

0.0 s

(0.0 - 1000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-37

(159F)

Comparator 2 Ineffective Time

Sets the length of time that CP2 [Comparator2 Limit Fault] is disabled.

0.0 s

(0.0 - 1000.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-40

(0B58)

Mbus Reg 15E0h bit0 Output Func

Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).

F

(0 - 1FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-41

(0B59)

Mbus Reg 15E0h bit1 Output Func

Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).

F

(0 - 1FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-42

(0B5A)

Mbus Reg 15E0h bit2 Output Func

Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).

F

(0 - 1FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-60

(1B46)

Expert

Term M1-M2 Secondary Function

Sets the second function for terminal M1-M2. Outputs the logical calculation results of the terminals assigned to functions by H2-01 [Term M1-M2 Function Selection].

F

(0 - FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-61

(1B47)

Expert

Terminal M1-M2 Logical Operation

Sets the logical operation for the functions set in H2-01 [Term M1-M2 Function Selection] and H2-60 [Term M1-M2 Secondary Function].

0

(0 - 8)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-62

(1B48)

Expert

Terminal M1-M2 Delay Time

Sets the minimum on time used to output the logical calculation results from terminal M1-M2.

0.1 s

(0.0 - 25.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-63

(1B49)

Expert

Term M3-M4 Secondary Function

Sets the second function for terminal M3-M4. Outputs the logical calculation results of the terminals assigned to functions by H2-02 [Term M3-M4 Function Selection].

F

(0 - FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-64

(1B4A)

Expert

Terminal M3-M4 Logical Operation

Sets the logical operation for the functions set in H2-02 [Term M3-M4 Function Selection] and H2-63 [Term M3-M4 Secondary Function].

0

(0 - 8)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-65

(1B4B)

Expert

Terminal M3-M4 Delay Time

Sets the minimum on time used to output the logical calculation results from terminal M3-M4.

0.1 s

(0.0 - 25.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-66

(1B4C)

Expert

Term M5-M6 Secondary Function

Sets the second function for terminal P1-C1. Outputs the logical calculation results of the terminals assigned to functions by H2-03 [Term P1-C1 Function Selection].

F

(0 - FF)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-67

(1B4D)

Expert

Terminal M5-M6 Logical Operation

Sets the logical operation for the functions set in H2-03 [Term P1-C1 Function Selection] and H2-66 [Term M5-M6 Secondary Function].

0

(0 - 8)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-68

(1B4E)

Expert

Terminal M5-M6 Delay Time

Sets the minimum on time used to output the logical calculation results from terminal P1-C1.

0.1 s

(0.0 - 25.0 s)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-69

(1B4F)

Expert

Digital Output4 Secondary Func

Sets the second function for terminal P2-C2. Outputs the logical calculation results of the terminals assigned to functions by H2-04 [Terminal P2-C2 Function Select].

F

(0 - A7)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-70

(11F9)

Expert

DigitalOutput4 Logical Operation

Sets the logical operation for the functions set in H2-04 [Term P2-C2 Function Selection] and H2-69 [Digital Output4 Secondary Func].

0

(0 - 8)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H2-71

(11FA)

Expert

Digital Output 4 Delay Time

Sets the minimum on time used to output the logical calculation results from terminal P2-C2.

0.1 s

(0.0 - 25.0 s)

Details