There is no PID feedback input.
|
-
Examine the MFAI terminal settings.
-
See if H3-02, H3-10, H3-06 = B [MFAI Function Select = PID Feedback] is set.
-
Make sure that the MFAI terminal settings agree with the signal inputs.
-
Examine the connection of the feedback signal.
-
Make sure that b5-xx [PID Control] is set correctly.
Note:
If there is no PID feedback input to the terminal, the detected value is 0, which causes a PID fault and also causes the drive to operate at maximum frequency.
|
|
The detection level and the target value do not agree.
|
Use H3-03, H3-11, H3-07 [Terminal A1, A2, A3 Gain Setting] to adjust PID target and feedback signal scaling.
Note:
PID control keeps the difference between the target value and detection value at 0. Set the input level for the values relative to each other.
|
|
Reverse drive output frequency and speed detection. When output frequency increases, the sensor detects a speed decrease.
|
Set b5-09 = 1 [PID Output Level Selection = Reverse output (reverse acting)].
|