CP2

Comparator 2 Limit Fault

The monitor value set in H2-26 [Comparator 2 Monitor Selection] was outside the range of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit].

Examine the monitor value and remove the cause of the fault.

Note:
  • The drive detects this error when the terminal is set to H2-01 to H2-04 = 67 [MFDO Function Selection = Comparator2].

  • Do a Fault Reset to clear the fault.

  • Set the stopping method for this fault in H2-35 [Comparator2 Protection Selection].