FbL
|
PID Feedback Loss
|
The FbL detection level is set incorrectly.
|
Adjust b5-13 [PID Feedback Loss Detection Lvl] and b5-14 [PID Feedback Loss Detection Time].
|
|
There is a problem with the PID feedback wiring.
|
Correct errors with the PID control wiring.
|
|
The feedback sensor is not operating correctly.
|
Examine the sensors on the control device side.
|
|
A fault occurred in the feedback input circuit of the drive.
|
Replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
|
Note:
-
The drive detects this fault if the PID feedback input is more than the level set in b5-13 for longer than b5-14.
-
Do a Fault Reset to clear the fault.
-
If the drive detects this fault, it will operate the motor as specified by the stop method set in b5-12 [Feedback Loss Detection Select].
|