Test Run Checklist

Examine the items in this checklist and check each item before a test run.

 

Checked

No.

Description

 

1

Correctly install and wire the drive as specified by this manual.

 

2

Energize the drive.

 

3

Set the voltage for the power supply in E1-01 [Input AC Supply Voltage].

Check the applicable items as specified by your control method.

Table 1. V/f Control [A1-02 = 0] and Closed Loop V/f Control [A1-02 = 1]

Checked

No.

Description

 

4

Select the best V/f pattern for your application and motor characteristics.

Example: For a motor with a rated frequency of 60 Hz, set E1-03 = 1 [V/f Pattern Selection = Const Trq, 60Hz base, 60Hz max] as a standard V/f pattern.

Table 2. Closed Loop V/f Control [A1-02 = 1]

Checked

No.

Description

 

5

Set F1-01 [Encoder 1 Pulse Count (PPR)] correctly and make sure that encoder pulse counting direction is correct.

 

6

Set C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1].

Table 3. Open Loop Vector Control [A1-02 = 2] or Closed Loop Vector Control [A1-02 = 3]

Checked

No.

Description

 

7

Decouple motor shafts and machines.

 

8

Refer to the information on the motor nameplate and set this data correctly:

  • Motor rated power (kW) to T1-02

  • Motor rated voltage (V) to T1-03

  • Motor rated current (A) to T1-04

  • Motor base frequency (Hz) to T1-05

  • Number of motor poles to T1-06

  • Motor base speed (min-1) to T1-07

 

9

Do Rotational Auto-Tuning.

Table 4. Closed Loop Vector Control [A1-02 = 3]

Checked

No.

Description

 

10

Set F1-01 [Encoder 1 Pulse Count (PPR)] and F1-05 [Encoder 1 Rotation Selection].

 

11

Set C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1].

Table 5. PM Open Loop Vector Control [A1-02 = 5]

Checked

No.

Description

 

12

Set E5-01 through E5-24 [PM Motor Settings].

Table 6. PM Advanced Open Loop Vector [A1-02 = 6]

Checked

No.

Description

 

13

Set E5-01 through E5-24 [PM Motor Settings].

 

14

Set C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1].

Table 7. PM Closed Loop Vector Control [A1-02 = 7]

Checked

No.

Description

 

15

Set E5-01 through E5-24 [PM Motor Settings].

 

16

Set C5-01 [ASR Proportional Gain 1] and C5-02 [ASR Integral Time 1].

 

17

Set F1-01 [Encoder 1 Pulse Count (PPR)] and F1-05 [Encoder 1 Rotation Selection].

 

18

Set E5-11 [Encoder Z-Pulse Offset].

 

Checked

No.

Description

 

19

The keypad will show “Rdy” after starting to operate the motor.

 

20

To give the Run command and frequency reference from the keypad, push [LO/RE selection key] to set to LOCAL Mode (when in LOCAL Mode, the LO/RE LED illuminates).

 

21

If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).

 

22

Set Heavy Duty or Normal Duty Mode with C6-01 [Normal / Heavy Duty Selection] to conform to the load condition.

 

23

Set E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload Protection Select] correctly for motor thermal protection.

 

24

Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency reference (in REMOTE Mode, the LO/RE LED turns OFF).

 

25

When terminal A1 is used for the frequency reference:

  • Voltage input

    • Set DIP Switch S1-1 on the drive to “V”.

    • Set H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar Reference)].

    • Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].

  • Current input

    • Set DIP Switch S1-1 on the drive to “I”.

    • Set H3-01 = 2, 3 [Terminal A1 Signal Level Select = 4 to 20 mA, 0 to 20 mA].

    • Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].

 

26

When terminal A2 is used for the frequency reference:

  • Voltage input

    • Set DIP Switch S1-2 on the drive to “V”.

    • Set H3-09 = 0, 1 [Terminal A2 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to 10 V (Bipolar Reference)].

    • Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].

  • Current input

    • Set DIP Switch S1-2 on the drive to “I”.

    • Set H3-09 = 2, 3 [Terminal A2 Signal Level Select = 4 to 20 mA, 0 to 20 mA].

    • Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].

 

27

When terminal A3 is used for the frequency reference:

  • Voltage input

    • Set DIP Switch S4 on the drive to analog input side.

    • Set DIP Switch S1-3 on the drive to “V”.

    • Set H3-05 = 0, 1 [Terminal A3 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar Reference)].

    • Set H3-06 = 0 [Terminal A3 Function Selection = Frequency Reference].

  • Current input

    • Set DIP Switch S4 on the drive to analog input side.

    • Set DIP Switch S1-3 on the drive to “I”.

    • Set H3-05 = 2, 3 [Terminal A3 Signal Level Select = 4 to 20 mA (Lower Limit at 4), 0 to 20 mA (Bipolar Reference)].

    • Set H3-06 = 0 [Terminal A3 Function Selection = Frequency Reference].

 

28

Make sure that the frequency reference reaches the necessary minimum and maximum values.

→ If drive operation is incorrect, make these adjustments:

Gain adjustment: Set the maximum voltage and current values, then adjust the analog input gain until the frequency reference reaches the necessary value. (For terminal A1 input: H3-03, for terminal A2 input: H3-11, for terminal A3 input: H3-07)

Bias adjustment: Set the maximum voltage/current values, then adjust the analog input bias until the frequency reference reaches the necessary minimum value. (For terminal A1 input: H3-04, for terminal A2 input: H3-12, for terminal A3 input: H3-08)