The keypad will show “Rdy” after starting to operate the motor.
|
| |
20
|
To give the Run command and frequency reference from the keypad, push to set to LOCAL Mode (when in LOCAL Mode, the LO/RE LED illuminates).
|
| |
21
|
If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
|
| |
22
|
Set Heavy Duty or Normal Duty Mode with C6-01 [Normal / Heavy Duty Selection] to conform to the load condition.
|
| |
23
|
Set E2-01 [Motor Rated Current (FLA)] and L1-01 [Motor Overload Protection Select] correctly for motor thermal protection.
|
| |
24
|
Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency reference (in REMOTE Mode, the LO/RE LED turns OFF).
|
| |
25
|
When terminal A1 is used for the frequency reference:
-
Voltage input
-
Set DIP Switch S1-1 on the drive to “V”.
-
Set H3-01 = 0, 1 [Terminal A1 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar Reference)].
-
Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].
-
Current input
-
Set DIP Switch S1-1 on the drive to “I”.
-
Set H3-01 = 2, 3 [Terminal A1 Signal Level Select = 4 to 20 mA, 0 to 20 mA].
-
Set H3-02 = 0 [Terminal A1 Function Selection = Frequency Reference].
|
| |
26
|
When terminal A2 is used for the frequency reference:
-
Voltage input
-
Set DIP Switch S1-2 on the drive to “V”.
-
Set H3-09 = 0, 1 [Terminal A2 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to 10 V (Bipolar Reference)].
-
Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].
-
Current input
-
Set DIP Switch S1-2 on the drive to “I”.
-
Set H3-09 = 2, 3 [Terminal A2 Signal Level Select = 4 to 20 mA, 0 to 20 mA].
-
Set H3-10 = 0 [Terminal A2 Function Selection = Frequency Reference].
|
| |
27
|
When terminal A3 is used for the frequency reference:
-
Voltage input
-
Set DIP Switch S4 on the drive to analog input side.
-
Set DIP Switch S1-3 on the drive to “V”.
-
Set H3-05 = 0, 1 [Terminal A3 Signal Level Select = 0 to 10V (Lower Limit at 0), -10 to +10V (Bipolar Reference)].
-
Set H3-06 = 0 [Terminal A3 Function Selection = Frequency Reference].
-
Current input
-
Set DIP Switch S4 on the drive to analog input side.
-
Set DIP Switch S1-3 on the drive to “I”.
-
Set H3-05 = 2, 3 [Terminal A3 Signal Level Select = 4 to 20 mA (Lower Limit at 4), 0 to 20 mA (Bipolar Reference)].
-
Set H3-06 = 0 [Terminal A3 Function Selection = Frequency Reference].
|
| |
28
|
Make sure that the frequency reference reaches the necessary minimum and maximum values.
→ If drive operation is incorrect, make these adjustments:
Gain adjustment: Set the maximum voltage and current values, then adjust the analog input gain until the frequency reference reaches the necessary value. (For terminal A1 input: H3-03, for terminal A2 input: H3-11, for terminal A3 input: H3-07)
Bias adjustment: Set the maximum voltage/current values, then adjust the analog input bias until the frequency reference reaches the necessary minimum value. (For terminal A1 input: H3-04, for terminal A2 input: H3-12, for terminal A3 input: H3-08)
|