No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o3-01

(0515)

Copy Keypad Function Selection

Sets the function that saves and copies drive parameters to a different drive with the keypad.

0
Copy Select
 
1
Backup (drive → keypad)

The parameter setting values are read from the drive and saved in the keypad.

2
Restore (keypad → drive)

Copies the parameter setting values saved in the keypad to a different drive.

3
Verify (check for mismatch)

Makes sure that the parameter setting values in the drive agree with the parameters saved in the keypad.

4
Erase (backup data of keypad)

Deletes the parameter setting values saved in the keypad.

0

(0 - 4)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o3-02

(0516)

Copy Allowed Selection

Sets the copy function when o3-01 = 1 [Copy Keypad Function Selection = Backup (drive → keypad)].

0
Disabled
 
1
Enabled
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o3-04

(0B3E)

Select Backup/Restore Location

Sets the storage location for drive parameters when you back up and restore parameters. This parameter is only available when using an LCD keypad.

0
Memory Location 1
 
1
Memory Location 2
 
2
Memory Location 3
 
3
Memory Location 4
 

0

(0 - 3)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o3-05

(0BDA)

Select Items to Backup/Restore

Sets which parameters are backed up, restored, and referenced. This parameter is only available when using an LCD keypad.

0
Standard Parameters
 
1
Standard + DWEZ Parameters
 

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o3-06

(0BDE)

Auto Parameter Backup Selection

Sets the function that automatically backs up parameters. This parameter is only available when using an LCD keypad.

0
Disabled
 
1
Enabled
 

1

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

o3-07

(0BDF)

Auto Parameter Backup Interval

Sets the interval at which the automatic parameter backup function saves parameters from the drive to the keypad.

Note:

This parameter is only available when using an LCD keypad.

0
Every 10 minutes
 
1
Every 30 minutes
 
2
Every 60 minutes
 
3
Every 12 hours
 

1

(0 - 3)

Details