Uv3
|
Soft Charge Answerback Fault
|
There is damage to the relay or contactor on the soft-charge bypass relay.
|
-
Re-energize the drive.
-
If the fault stays, replace the control board or the drive.
-
Monitor U4-06 [PreChargeRelayMainte] shows the performance life of the soft-charge bypass relay. If U4-06 is more than 90%, replace the board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
|
|
Air inside the drive is too hot.
|
Decrease the ambient temperature of the drive.
|
|
|