GF
|
Ground Fault
|
Overheating caused damage to the motor or the motor insulation is not satisfactory.
|
Measure the motor insulation resistance, and replace the motor if there is electrical conduction or unserviceable insulation.
|
|
The motor main circuit cable is contacting ground to make a short circuit.
|
-
Examine the motor main circuit cable for damage, and repair short circuits.
-
Measure the resistance between the motor main circuit cable and the ground terminal. If there is electrical conduction, replace the cable.
|
|
An increase in the stray capacitance of the cable and the ground terminal caused an increase in the leakage current.
|
-
If the wiring length of the cable is more than 100 m, decrease the carrier frequency.
-
Decrease the stray capacitance.
|
|
There was a problem with the drive hardware.
|
Replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
|
Note:
-
The drive detects this fault if a current short to ground was more than 50% of rated current on the output side of the drive.
-
Do a Fault Reset to clear the fault.
-
L5-08 [Fault Reset Enable Select Grp2] disables the Auto Restart function.
|