Shows the hold value of the peak value (rms) for the drive output current.
Use U4-14 [PeakHold Output Freq] to show the drive output frequency at the time that the drive holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power supply. The drive keeps the value that was under hold during baseblock (during stop).
The keypad shows the value of U4-13 in amperes (A). When you use MEMOBUS/Modbus communications to show the monitor, the current is “8192 = drive rated current (A)”. Use the formula: “Numerals being displayed / 8192 × drive rated current (A)” to use the MEMOBUS/Modbus communication current value shown in the monitor.
When the drive model changes, the display units for this parameter also change.
-
0.01 A: 2004 - 2042, 4002 - 4023
-
0.1 A: 2056 - 2415, 4031 - 4675
-
1 A: 4810 - 4H12
|
No signal output available
|