oPE05
|
Run Cmd/Freq Ref Source Sel Err
|
The setting to assign the Run command or frequency reference to an option card or the pulse train input is incorrect.
|
Correct the parameter settings.
|
|
b1-01 = 3 [Frequency Reference Selection 1 = Option PCB] is set, but there is no option card connected to the drive.
|
Connect an option card to the drive.
|
|
b1-02 = 3 [Run Command Selection 1 = Option PCB] is set, but there is no option card connected to the drive.
|
|
The following parameters are set at the same time:
|
Set H6-01 = 0.
|
|
The following parameters are set at the same time:
-
F3-01 = 6 [Digital Input Function Selection = BCD (5-digit), 0.01 Hz]
-
F3-03 = 0, 1 [Digital Input Data Length Select = 8-bit, 12-bit]
|
Set F3-03 = 2 [16-bit].
|
|
These parameters are set and there is an AI-A3 option card connected to the drive:
-
H1-xx = 2 [External Reference 1/2 Selection]
-
b1-15 = 3 [Frequency Reference Selection 2 = Option PCB]
-
F2-01 = 0 [Analog Input Function Selection = 3 Independent Channels]
|
Correct the parameter settings.
|