Parameters Changed by E1-03 [V/f Pattern Selection]

The values for parameters A1-02 [Control Method Selection] and E1-03 [V/f Pattern Selection] change the default settings for the parameters in these tables:

Table 1. Parameters Changed by E1-03 (2004 - 2021 and 4002 - 4012)

No.

E1-03

E1-04

E1-05 1

E1-06

E1-07

E1-08 1

E1-09

E1-10 1

Unit

-

Hz

V

Hz

Hz

V

Hz

V

Setting Value

0

50.0

200.0

50.0

2.5

15.0

1.3

9.0

1

60.0

200.0

60.0

3.0

15.0

1.5

9.0

2

60.0

200.0

50.0

3.0

15.0

1.5

9.0

3

72.0

200.0

60.0

3.0

15.0

1.5

9.0

4

50.0

200.0

50.0

25.0

35.0

1.3

8.0

5

50.0

200.0

50.0

25.0

50.0

1.3

9.0

6

60.0

200.0

60.0

30.0

35.0

1.5

8.0

7

60.0

200.0

60.0

30.0

50.0

1.5

9.0

8

50.0

200.0

50.0

2.5

19.0

1.3

11.0

9

50.0

200.0

50.0

2.5

24.0

1.3

13.0

A

60.0

200.0

60.0

3.0

19.0

1.5

11.0

B

60.0

200.0

60.0

3.0

24.0

1.5

15.0

C

90.0

200.0

60.0

3.0

15.0

1.5

9.0

D

120.0

200.0

60.0

3.0

15.0

1.5

9.0

E

180.0

200.0

60.0

3.0

15.0

1.5

9.0

F

60.0 2

200.0 2

60.0 2

3.0 2

15.0 2

1.5 2

9.0 2

Control Method Selection

(A1-02 Setting)

OLV (2)

60.0

200.0

60.0

3.0

11.0

0.5

2.0

CLV (3)

60.0

200.0

60.0

0.0

0.0

0.0

0.0

OLV/PM (5)

3

3

3

-

-

3

-

AOLV/PM (6)

3

3

3

-

-

3

-

CLV/PM (7)

3

3

3

-

-

0.0

-

 
Table 2. Parameters Changed by E1-03 (2030 - 2211 and 4018 - 4103)

No.

E1-03

E1-04

E1-05 1

E1-06

E1-07

E1-08 1

E1-09

E1-10 1

Unit

-

Hz

V

Hz

Hz

V

Hz

V

Setting Value

0

50.0

200.0

50.0

2.5

14.0

1.3

7.0

1

60.0

200.0

60.0

3.0

14.0

1.5

7.0

2

60.0

200.0

50.0

3.0

14.0

1.5

7.0

3

72.0

200.0

60.0

3.0

14.0

1.5

7.0

4

50.0

200.0

50.0

25.0

35.0

1.3

6.0

5

50.0

200.0

50.0

25.0

50.0

1.3

7.0

6

60.0

200.0

60.0

30.0

35.0

1.5

6.0

7

60.0

200.0

60.0

30.0

50.0

1.5

7.0

8

50.0

200.0

50.0

2.5

18.0

1.3

9.0

9

50.0

200.0

50.0

2.5

23.0

1.3

11.0

A

60.0

200.0

60.0

3.0

18.0

1.5

9.0

B

60.0

200.0

60.0

3.0

23.0

1.5

13.0

C

90.0

200.0

60.0

3.0

14.0

1.5

7.0

D

120.0

200.0

60.0

3.0

14.0

1.5

7.0

E

180.0

200.0

60.0

3.0

14.0

1.5

7.0

F

60.0 2

200.0 2

60.0 2

3.0 2

14.0 2

1.5 2

7.0 2

Control Method Selection

(A1-02 Setting)

OLV (2)

60.0

200.0

60.0

3.0

11.0

0.5

2.0

CLV (3)

60.0

200.0

60.0

0.0

0.0

0.0

0.0

OLV/PM (5)

3

3

3

-

-

3

-

AOLV/PM (6)

3

3

3

-

-

3

-

CLV/PM (7)

3

3

3

-

-

0.0

-

Table 3. Parameters Changed by E1-03 (2257 - 2415 and 4140 - 4H12)

No.

E1-03

E1-04

E1-05 1

E1-06

E1-07

E1-08 1

E1-09

E1-10 1

Unit

-

Hz

V

Hz

Hz

V

Hz

V

Setting Value

0

50.0

200.0

50.0

2.5

12.0

1.3

6.0

1

60.0

200.0

60.0

3.0

12.0

1.5

6.0

2

60.0

200.0

50.0

3.0

12.0

1.5

6.0

3

72.0

200.0

60.0

3.0

12.0

1.5

6.0

4

50.0

200.0

50.0

25.0

35.0

1.3

5.0

5

50.0

200.0

50.0

25.0

50.0

1.3

6.0

6

60.0

200.0

60.0

30.0

35.0

1.5

5.0

7

60.0

200.0

60.0

30.0

50.0

1.5

6.0

8

50.0

200.0

50.0

2.5

15.0

1.3

7.0

9

50.0

200.0

50.0

2.5

20.0

1.3

9.0

A

60.0

200.0

60.0

3.0

15.0

1.5

7.0

B

60.0

200.0

60.0

3.0

20.0

1.5

11.0

C

90.0

200.0

60.0

3.0

12.0

1.5

6.0

D

120.0

200.0

60.0

3.0

12.0

1.5

6.0

E

180.0

200.0

60.0

3.0

12.0

1.5

6.0

F

60.0 2

200.0 2

60.0 2

3.0 2

12.0 2

1.5 2

6.0 2

Control Method Selection

(A1-02 Setting)

OLV (2)

60.0

200.0

60.0

3.0

11.0

0.5

2.0

CLV (3)

60.0

200.0

60.0

0.0

0.0

0.0

0.0

OLV/PM (5)

3

3

3

-

-

3

-

AOLV/PM (6)

3

3

3

-

-

3

-

CLV/PM (7)

3

3

3

-

-

0.0

-

1

This is the value for 200 V class drives. Double the value for 400 V class drives.

2

These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as those for the V/f pattern when E1-03 = 1 [Const Trq, 60Hz base, 60Hz max].

3

The default setting varies depending on the setting of E5-01 [PM Motor Code Selection].