Figure 1. Keypad Functions and Display Levels
Note:
  • Energize the drive with factory defaults to show the Initial Setup screen. Push [F2 Key] [Home] to show the HOME screen.

    • Select [No] from the [Show Initial Setup Screen] setting to not display the Initial Setup screen.

  • Push [LEFT Key] from the Home screen to show drive monitors.

  • Push [ENTER Key] to set d1-01 [Reference 1] when the Home screen shows U1-01 [Frequency Reference] in LOCAL Mode.

  • The keypad will show [Rdy] when the drive is in Drive Mode. The drive is prepared to accept a Run command.

  • Set b1-08 [Run Command Select in PRG Mode] to accept or reject a Run command from an external source while in Programming Mode.

    • Set b1-08 = 0 [Disregard RUN while Programming] to reject the Run command from an external source while in Programming Mode (default).

    • Set b1-08 = 1 [Accept RUN while Programming] to accept the Run command from an external source while in Programming Mode.

    • Set b1-08 = 2 [Allow Programming Only at Stop] to prevent changes from Drive Mode to Programming Mode while the drive is operating.

Table 1. Drive Mode Screens and Functions

Mode

Keypad Screen

Function

Drive Mode

Monitors

Sets monitor items to display.

Programming Mode

Parameters

Changes parameter settings.

User Custom Parameters

Shows the User Parameters.

Parameter Backup/Restore

Saves parameters to the keypad as backup.

Modified Parameters/Fault Log

Shows modified parameters and fault history.

Auto-Tuning

Auto-Tunes the drive.

Initial Setup Screen

Changes initial settings.

Diagnostic Tools

Sets data logs and backlight.