You can use pulse train monitor output terminal MP for sourcing mode or for sinking mode.

  • Use for sourcing mode

    The load impedance changes the voltage level of the pulse train output signal.

     

    Load Impedance

    RL(kΩ)

    Output Voltage

    VMP(V)

    1.5 kΩ or more

    5 V or more

    4.0 kΩ or more

    8 V or more

    10 kΩ or more

    10 V or more

    Note:

    Use the formula in Figure 1 to calculate the necessary load resistance (kΩ) to increase output voltage VMP(V).

    Figure 1. Wiring to Use Pulse Train Output in Sourcing Mode
    • Load Impedance
  • Use in sinking mode

    The external power supply changes the voltage level of the pulse train output signal. Keep the voltage from an external source between 10.8 Vdc to 16.5 Vdc. Adjust the load impedance to keep the current at 16 mA or lower.

     

    External Power Supply (V)

    Load Impedance (kΩ)

    Sinking current (mA)

    10.8 Vdc to 16.5 Vdc

    1.0 kΩ or more

    16 mA maximum

    Figure 2. Wiring to Use Pulse Train Output in Sinking Mode
    • External power supply
    • Load Impedance
    • Sinking current