No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-01

(11E4)

Motor Type Selection

Sets the type of motor.

0
Induction (IM)
 
1
Permanent Magnet (PM)
 
2
Synchronous Reluctance (SynRM)
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-02

(11E5)

Maximum Speed

Sets the maximum speed of the motor.

Determined by E9-01

(40.0 - 120.0 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-03

(11E6)

Rated Speed

Sets the rated rotation speed of the motor.

Determined by E9-01

(100 - 7200 min-1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-04

(11E7)

Base Frequency

Sets the rated frequency of the motor.

Determined by E9-01

(40.0 - 120.0 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-05

(11E8)

Motor Rated Voltage

Sets the rated voltage of the motor.

200 V Class: 200.0 V,

400 V Class: 400.0 V

(200 V Class: 0.0 - 255.0 V, 400 V Class: 0.0 - 510.0 V)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-06

(11E9)

Motor Rated Current (FLA)

Sets the motor rated current in amps.

Determined by E9-01 and o2-04

(10% to 200% of the drive rated current)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-07

(11EA)

PM Motor Rated Power

Sets the motor rated output in the units from o1-58 [Motor Power Unit Selection].

Note:

On drive models 2xxx, and 4002 to 4675, the setting unit is 0.01 kW. The setting range is 0.00 kW to 650.00 kW (0.00 HP to 650.00 HP).

On drive models 4810 to 4H12, the setting unit is 0.1 kW. The setting range is 0.0 kW to 1000.0 kW (0.0 HP to 1340.5 HP).

Determined by E9-02 and o2-04

(0.00 - 1000.0)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-08

(11EB)

Motor Pole Count

Sets the number of motor poles.

4

(2 to 120)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-09

(11EC)

Motor Rated Slip

Sets the motor rated slip.

0.000 Hz

(0.000 - 20.000 Hz)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

E9-10

(11ED)

Motor Line-to-Line Resistance

Sets the line-to-line resistance for the motor stator windings.

Note:

On drive models 4810 to 4H12, the unit is mΩ, and the setting range is 0.000 mΩ to 65.000 mΩ.

Determined by o2-04

(0.000 - 65.000 Ω)

Details