No. (Hex.) Name Description Default (Range) Ref. b2-01 (0189) DC Injection/Zero SpeedThreshold Sets the frequency to start DC Injection Braking, Short Circuit Braking, or Zero Servo near the end of a stop ramp. Note: This parameter is available when b1-03 = 0 [Stopping Method Selection = Ramp to Stop]. Determined by A1-02 (0.0 - 10.0 Hz) Details No. (Hex.) Name Description Default (Range) Ref. b2-02 (018A) DC Injection Braking Current Sets the DC Injection Braking current as a percentage of the drive rated current. 50% (0 - 100%) Details No. (Hex.) Name Description Default (Range) Ref. b2-03 (018B) DC Inject Braking Time at Start Sets the DC Injection Braking Time at stop. Sets the time of Zero Speed Control at start when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]. A1-02 = 4: 0.30 s Other than A1-02 = 4: 0.00 s (0.00 - 10.00 s) Details No. (Hex.) Name Description Default (Range) Ref. b2-04 (018C) DC Inject Braking Time at Stop Sets the DC Injection Braking Time at stop. Sets the time of Zero Speed Control at stop when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]. Determined by A1-02 (0.00 - 10.00 s) Details No. (Hex.) Name Description Default (Range) Ref. b2-08 (0190) Magnetic Flux Compensation Value Sets how much current the drive injects when DC Injection Braking at Start starts (Initial Excitation) as a percentage of E2-03 [Motor No-Load Current]. 0% (0 - 1000%) Details No. (Hex.) Name Description Default (Range) Ref. b2-12 (01BA) Short Circuit Brake Time @ Start Sets the Short Circuit Braking time at start. 0.00 s (0.00 - 25.50 s) Details No. (Hex.) Name Description Default (Range) Ref. b2-13 (01BB) Short Circuit Brake Time @ Stop Sets the Short Circuit Braking time at stop. A1-02 = 8: 0.00 s Other than A1-02 = 8: 0.50 s (0.00 - 25.50 s) Details No. (Hex.) Name Description Default (Range) Ref. b2-18 (0177) Short Circuit Braking Current Sets the Short Circuit Braking Current as a percentage of the motor rated current. Note: Parameter A1-02 [Control Method Selection] selects which parameter is the motor rated current. A1-02 = 5, 6 [OLV/PM, AOLV/PM]: E5-03 [PM Motor Rated Current (FLA)] A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)] 100.0% (0.0 - 200.0%) Details