01
|
Function Code Error
|
The PLC set a function code that was not 03, 08, or 10 (Hex.)
|
|
02
|
Register Number Error
|
|
|
03
|
Bit Count Error
|
-
Read and write data quantities are more than the 1 to 16 range. (Command message data quantity is disabled.)
-
The data that was read from non-consecutive holding registers contained more than 120 bytes.
-
The data to be written to non-consecutive holding registers contained more than 60 bytes.
-
In the write mode, the number of bytes in the message is not the number of data × 2.
|
|
21
|
Data Setting Error
|
|
|
22
|
Write Mode Error
|
-
Tried to write a disabled parameter during run.
-
When there was a CPF06 [Control Circuit Error], the master tried to write a parameter other than one of these:
-
A1-00 [Language Selection]
-
A1-01 [Access Level Selection]
-
A1-02 [Control Method Selection]
-
A1-03 [Initialize Parameters]
-
A1-04 [Password]
-
A1-05 [Password Setting]
-
E1-03 [V/f Pattern Selection]
-
o2-04 [Drive Model (KVA) Selection]
-
Writes the read-only data.
|
|
23
|
DC Bus Undervoltage Write Error
|
During Uv [DC Bus Undervoltage], a Uv write disabled parameter was written.
|
|
24
|
Error Writing Data During Parameter Processing
|
Tried to write a parameter from the master during parameter processing on the drive side.
|
|
25
|
Writing into EEPROM Disabled
|
Writing into EEPROM write is disabled, but EEPROM write was executed from MEMOBUS/Modbus communications. When this error occurs, the keypad shows a message and the drive continues operation.
|