Jump to main content

Three-Phase 400 V Class

 

No. 1

Name

Unit

Default

-

Drive Model

-

4002

4004

4005

4007

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

92

93

94

95

E2-11

(E4-11)

Motor Rated Power

kW

0.4

0.75

1.1

1.5

1.5

2.2

2.2

3.0

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

100

100

100

b3-06

Speed Estimation Current Level 1

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

-

576.4

447.4

447.4

338.8

338.8

313.6

313.6

265.7

C5-17

(C5-37)

Motor Inertia

kgm2

0.0015

0.0028

0.0028

0.0068

0.0068

0.0088

0.0088

0.0158

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

1

1.6

1.6

3.1

3.1

4.2

4.2

5.7

E2-02

(E4-02)

Motor Rated Slip

Hz

2.9

2.6

2.6

2.5

2.5

3

3

2.7

E2-03

(E4-03)

Motor No-Load Current

A

0.6

0.8

0.8

1.4

1.4

1.5

1.5

1.9

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 2

38.198

22.459

22.459

10.1

10.1

6.495

6.495

4.360

E2-06

(E4-06)

Motor Leakage Inductance

%

18.2

14.3

14.3

18.3

18.3

18.7

18.7

19

E2-10

(E4-10)

Motor Iron Loss

W

14

26

26

53

53

77

77

105

E5-01

PM Motor Code Selection

-

1232

1232

1233

1233

1235

1235

1236

1236

L2-02

Power Loss Ride Through Time

s

0.1

0.1

0.2

0.2

0.3

0.3

0.5

0.5

L2-03

Minimum Baseblock Time

s

0.2

0.3

0.3

0.4

0.4

0.5

0.5

0.5

L2-04

Powerloss V/f Recovery Ramp Time

s

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

380

380

380

380

380

380

L3-24

Motor Accel Time @ Rated Torque

s

0.178

0.142

0.142

0.166

0.166

0.145

0.145

0.145

L8-02

Overheat Alarm Level

°C

100

100

105

105

112

112

100

100

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

1

1

1

1

1

1

1

1

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

10

10

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.178

0.142

0.142

0.166

0.166

0.145

0.145

0.145

 
 

No. 1

Name

Unit

Default

-

Drive Model

-

4009

4012

4018

4023

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

96

97

99

9A

E2-11

(E4-11)

Motor Rated Power

kW

3.0

4.0

4.0

5.5

5.5

7.5

7.5

11

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

100

100

100

b3-06

Speed Estimation Current Level 1

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

-

265.7

245.8

245.8

189.5

189.5

145.38

145.38

140.88

C5-17

(C5-37)

Motor Inertia

kgm2

0.0158

0.0158

0.0158

0.0255

0.026

0.037

0.037

0.053

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

5.7

7

7

9.8

9.8

13.3

13.3

19.9

E2-02

(E4-02)

Motor Rated Slip

Hz

2.7

2.7

2.7

1.5

1.5

1.3

1.3

1.7

E2-03

(E4-03)

Motor No-Load Current

A

1.9

2.3

2.3

2.6

2.6

4

4

5.6

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 2

4.360

3.333

3.333

1.595

1.595

1.152

1.152

0.922

E2-06

(E4-06)

Motor Leakage Inductance

%

19

19.3

19.3

18.2

18.2

15.5

15.5

19.6

E2-10

(E4-10)

Motor Iron Loss

W

105

130

130

193

193

263

263

385

E5-01

PM Motor Code Selection

-

FFFF

FFFF

1238

1238

123A

123A

123B

123B

L2-02

Power Loss Ride Through Time

s

0.5

0.5

0.5

0.5

0.8

0.8

1

1

L2-03

Minimum Baseblock Time

s

0.5

0.6

0.6

0.7

0.7

0.8

0.8

0.9

L2-04

Powerloss V/f Recovery Ramp Time

s

0.3

0.3

0.3

0.3

0.3

0.3

0.3

0.3

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

380

380

380

380

380

380

L3-24

Motor Accel Time @ Rated Torque

s

0.145

0.154

0.154

0.168

0.168

0.175

0.175

0.265

L8-02

Overheat Alarm Level

°C

100

100

100

100

105

105

105

105

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

1

1

1

1

1

1

1

1

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

10

10

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.145

0.154

0.154

0.168

0.168

0.175

0.175

0.265

 

No. 1

Name

Unit

Default

-

Drive Model

-

4031

4038

4044

4060

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

9C

9D

9E

9F

E2-11

(E4-11)

Motor Rated Power

kW

11

15

15

18.5

18.5

22

22

30

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

100

100

100

b3-06

Speed Estimation Current Level 1

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

b8-04

Energy Saving Coefficient Value

-

140.88

126.26

126.26

115.74

115.74

103.58

103.58

92.54

C5-17

(C5-37)

Motor Inertia

kgm2

0.053

0.076

0.076

0.138

0.138

0.165

0.165

0.220

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

19.9

26.5

26.5

32.9

32.9

38.6

38.6

52.3

E2-02

(E4-02)

Motor Rated Slip

Hz

1.7

1.6

1.6

1.67

1.67

1.7

1.7

1.8

E2-03

(E4-03)

Motor No-Load Current

A

5.6

7.6

7.6

7.8

7.8

9.2

9.2

10.9

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 2

0.922

0.55

0.55

0.403

0.403

0.316

0.316

0.269

E2-06

(E4-06)

Motor Leakage Inductance

%

19.6

17.2

17.2

20.1

20.1

23.5

23.5

20.7

E2-10

(E4-10)

Motor Iron Loss

W

385

440

440

508

508

586

586

750

E5-01

PM Motor Code Selection

-

123D

123D

123E

123E

123F

123F

1240

1240

L2-02

Power Loss Ride Through Time

s

2

2

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

0.9

1

1

1

1

1

1

1.1

L2-04

Powerloss V/f Recovery Ramp Time

s

0.3

0.6

0.6

0.6

0.6

0.6

0.6

0.6

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

380

380

380

380

380

380

L3-24

Motor Accel Time @ Rated Torque

s

0.265

0.244

0.244

0.317

0.317

0.355

0.355

0.323

L8-02

Overheat Alarm Level

°C

115

115

120

120

120

120

130

137

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

2

2

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

10

10

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.265

0.244

0.244

0.317

0.317

0.355

0.355

0.323

 

No. 1

Name

Unit

Default

-

Drive Model

-

4075

4089

4103

4140

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

A1

A2

A3

A4

E2-11

(E4-11)

Motor Rated Power

kW

30

37

37

45

45

55

55

75

b3-04

V/f Gain during Speed Search

%

100

100

100

100

100

80

80

60

b3-06

Speed Estimation Current Level 1

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.7

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.8

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

0.50

0.50

0.50

0.50

0.50

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

-

92.54

76.32

76.32

71.56

71.56

67.2

67.2

46.2

C5-17

(C5-37)

Motor Inertia

kgm2

0.220

0.273

0.273

0.333

0.333

0.490

0.49

0.90

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

52.3

65.6

65.6

79.7

79.7

95

95

130

E2-02

(E4-02)

Motor Rated Slip

Hz

1.8

1.33

1.33

1.6

1.6

1.46

1.46

1.39

E2-03

(E4-03)

Motor No-Load Current

A

10.9

19.1

19.1

22

22

24

24

36

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 2

0.269

0.155

0.155

0.122

0.122

0.088

0.088

0.092

E2-06

(E4-06)

Motor Leakage Inductance

%

20.7

18.8

18.8

19.9

19.9

20

20

20

E2-10

(E4-10)

Motor Iron Loss

W

750

925

925

1125

1125

1260

1260

1600

E5-01

PM Motor Code Selection

-

1242

1242

1243

1243

1244

1244

1245

1245

L2-02

Power Loss Ride Through Time

s

2

2

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

1.1

1.1

1.1

1.2

1.2

1.2

1.2

1.3

L2-04

Powerloss V/f Recovery Ramp Time

s

0.6

0.6

0.6

0.6

0.6

1

1

1

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

380

380

380

380

380

380

L3-24

Motor Accel Time @ Rated Torque

s

0.323

0.32

0.32

0.387

0.387

0.317

0.317

0.533

L8-02

Overheat Alarm Level

°C

120

120

115

115

126

120

120

120

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

2

2

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

10

10

10

10

10

10

30

30

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.323

0.32

0.32

0.387

0.387

0.317

0.317

0.533

 

No. 1

Name

Unit

Default

-

Drive Model

-

4168

4208

4250

4296

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

A5

A6

A7

A8

E2-11

(E4-11)

Motor Rated Power

kW

75

90

90

110

110

150

150

185

b3-04

V/f Gain during Speed Search

%

60

60

60

60

60

60

60

60

b3-06

Speed Estimation Current Level 1

-

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

2.00

2.00

2.00

2.00

2.00

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

-

46.2

38.91

38.91

36.23

36.23

32.79

32.79

30.13

C5-17

(C5-37)

Motor Inertia

kgm2

0.90

1.10

1.10

1.90

1.90

2.10

2.10

3.30

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

130

156

156

190

190

223

223

270

E2-02

(E4-02)

Motor Rated Slip

Hz

1.39

1.4

1.4

1.4

1.4

1.38

1.38

1.35

E2-03

(E4-03)

Motor No-Load Current

A

36

40

40

49

49

58

58

70

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 2

0.092

0.056

0.056

0.046

0.046

0.035

0.035

0.029

E2-06

(E4-06)

Motor Leakage Inductance

%

20

20

20

20

20

20

20

20

E2-10

(E4-10)

Motor Iron Loss

W

1600

1760

1760

2150

2150

2350

2350

2850

E5-01

PM Motor Code Selection

-

1246

1246

1247

1247

1248

1248

1249

1249

L2-02

Power Loss Ride Through Time

s

2

2

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

1.3

1.5

1.5

1.7

1.7

1.7

1.7

1.8

L2-04

Powerloss V/f Recovery Ramp Time

s

1

1

1

1

1

1

1

1

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

380

380

380

380

380

380

L3-24

Motor Accel Time @ Rated Torque

s

0.533

0.592

0.592

0.646

0.646

0.673

0.673

0.777

L8-02

Overheat Alarm Level

°C

110

110

105

105

120

120

120

120

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

2

2

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

30

30

30

30

30

30

30

30

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.533

0.592

0.592

0.646

0.646

0.673

0.673

0.777

 

No. 1

Name

Unit

Default

-

Drive Model

-

4371

4389

4453

4568

C6-01

Normal / Heavy Duty Selection

-

HD

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

A9

AA

AC

AD

E2-11

(E4-11)

Motor Rated Power

kW

185

220

220

260

260

300

300

335

b3-04

V/f Gain during Speed Search

%

60

60

60

60

60

60

60

60

b3-06

Speed Estimation Current Level 1

-

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

1.0

1.0

1.0

1.0

1.0

1.0

b3-08

Speed Estimation ACR P Gain

-

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

2.00

2.00

2.00

2.00

2.00

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

-

30.13

30.57

30.57

27.13

27.13

21.76

21.76

21.76

C5-17

(C5-37)

Motor Inertia

kgm2

3.30

3.60

3.60

4.10

4.10

6.50

6.50

11.00

C6-02

Carrier Frequency Selection

-

1

7

1

7

1

7

1

7

E2-01

(E4-01)

Motor Rated Current (FLA)

A

270

310

310

370

370

500

500

500

E2-02

(E4-02)

Motor Rated Slip

Hz

1.35

1.3

1.3

1.3

1.3

1.25

1.25

1.25

E2-03

(E4-03)

Motor No-Load Current

A

70

81

81

96

96

130

130

130

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 2

0.029

0.025

0.025

0.02

0.02

0.014

0.014

0.014

E2-06

(E4-06)

Motor Leakage Inductance

%

20

20

20

20

20

20

20

20

E2-10

(E4-10)

Motor Iron Loss

W

2850

3200

3200

3700

3700

4700

4700

4700

E5-01

PM Motor Code Selection

-

124A

124A

124A

124A

124A

124A

124A

124A

L2-02

Power Loss Ride Through Time

s

2

2

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

1.8

1.9

1.9

2

2

2.1

2.1

2.1

L2-04

Powerloss V/f Recovery Ramp Time

s

1

1

1.8

1.8

1.8

2

2

2

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

380

380

380

380

380

380

L3-24

Motor Accel Time @ Rated Torque

s

0.777

0.864

0.864

0.91

0.91

1.392

1.392

1.392

L8-02

Overheat Alarm Level

°C

125

125

125

125

110

110

125

115

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

2

2

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

30

30

100

100

100

100

100

100

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

0.777

0.864

0.864

0.91

0.91

1.392

1.392

1.392

 

No. 1

Name

Unit

Default

-

Drive Model

-

4675

4810

4930

4H11

C6-01

Normal / Heavy Duty Selection

-

HD1

ND

HD

ND

HD

ND

HD

ND

0

1

0

1

0

1

0

1

o2-04

Drive Model (KVA) Selection

Hex.

AE

B0

B1

B2

E2-11

(E4-11)

Motor Rated Power

kW

315

355

450

525

525

600

600

675

b3-04

V/f Gain during Speed Search

%

60

60

40

40

40

40

40

40

b3-06

Speed Estimation Current Level 1

-

0.7

0.7

0.7

0.7

0.7

0.7

0.7

0.7

b3-07

Speed Estimation Current Level 2

-

1.0

1.0

3.0

2.0

3.0

2.0

3.0

2.0

b3-08

Speed Estimation ACR P Gain

-

0.8

0.8

0.8

0.8

0.8

0.8

0.8

0.8

b3-26

Direction Determination Level

-

1000

1000

1000

1000

1000

1000

1000

1000

b8-03

Energy Saving Filter Time

s

2.00

2.00

2.00

2.00

2.00

2.00

2.00

2.00

b8-04

Energy Saving Coefficient Value

-

21.76

23.84

23.84

21.4

21.4

20.26

20.26

18.12

C5-17

(C5-37)

Motor Inertia

kgm2

11.00

12.00

12.00

13.00

13.00

14.00

14.00

18.00

C6-02

Carrier Frequency Selection

-

1

7

1

1

1

1

1

1

E2-01

(E4-01)

Motor Rated Current (FLA)

A

500

650

650

800

800

900

900

1090

E2-02

(E4-02)

Motor Rated Slip

Hz

1.25

1

1

1

1

0.9

0.9

0.8

E2-03

(E4-03)

Motor No-Load Current

A

130

130

130

160

160

180

180

218

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 3

0.014

0.012

12.000

10.000

10.000

9.000

9.000

7.000

E2-06

(E4-06)

Motor Leakage Inductance

%

20

20

20

20

20

20

20

20

E2-10

(E4-10)

Motor Iron Loss

W

4700

5560

5560

7050

7050

7833

7833

9870

E5-01

PM Motor Code Selection

-

FFFF

FFFF

-

-

-

-

-

-

L2-02

Power Loss Ride Through Time

s

2

2

2

2

2

2

2

2

L2-03

Minimum Baseblock Time

s

2.1

2.3

2.3

2.8

2.8

3.1

3.1

4

L2-04

Powerloss V/f Recovery Ramp Time

s

2

2.2

2.2

2.6

2.6

3

3

3.8

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

380

380

380

380

380

380

L3-24

Motor Accel Time @ Rated Torque

s

1.392

1.667

1.667

2

2

2.222

2.222

2.857

L8-02

Overheat Alarm Level

°C

133

133

120

120

120

120

120

120

L8-09

Output Ground Fault Detection

-

1

1

1

1

1

1

1

1

L8-38

Carrier Frequency Reduction

-

2

2

2

2

2

2

2

2

n1-01

Hunting Prevention Selection

-

2

2

2

2

2

2

2

2

n1-03

Hunting Prevention Time Constant

ms

100

100

100

100

100

100

100

100

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

0.50

0.50

0.50

0.50

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

1.392

1.667

1.667

2

2

2.222

2.222

2.857

 
 

No. 1

Name

Unit

 

-

Drive Model

-

4H12

C6-01

Normal / Heavy Duty Selection

-

HD

ND

0

1

o2-04

Drive Model (KVA) Selection

Hex.

B3

E2-11

(E4-11)

Motor Rated Power

kW

675

750

b3-04

V/f Gain during Speed Search

%

40

40

b3-06

Speed Estimation Current Level 1

-

0.7

0.7

b3-07

Speed Estimation Current Level 2

-

3.0

2.0

b3-08

Speed Estimation ACR P Gain

-

0.8

0.8

b3-26

Direction Determination Level

-

1000

1000

b8-03

Energy Saving Filter Time

s

2.00

2.00

b8-04

Energy Saving Coefficient Value

-

18.12

17.06

C5-17

(C5-37)

Motor Inertia

kgm2

18.00

18.00

C6-02

Carrier Frequency Selection

-

1

1

E2-01

(E4-01)

Motor Rated Current (FLA)

A

1090

1200

E2-02

(E4-02)

Motor Rated Slip

Hz

0.8

0.7

E2-03

(E4-03)

Motor No-Load Current

A

218

240

E2-05

(E4-05)

Motor Line-to-Line Resistance

Ω/mΩ 3

7.000mΩ

6.000mΩ

E2-06

(E4-06)

Motor Leakage Inductance

%

20

20

E2-10

(E4-10)

Motor Iron Loss

W

9870

11123

E5-01

PM Motor Code Selection

-

-

-

L2-02

Power Loss Ride Through Time

s

2

2

L2-03

Minimum Baseblock Time

s

4

4.6

L2-04

Powerloss V/f Recovery Ramp Time

s

3.8

4.5

L2-05

Undervoltage Detection Lvl (Uv1)

-

380

380

L3-24

Motor Accel Time @ Rated Torque

s

2.857

3.333

L8-02

Overheat Alarm Level

°C

120

120

L8-09

Output Ground Fault Detection

-

1

1

L8-38

Carrier Frequency Reduction

-

2

2

n1-01

Hunting Prevention Selection

-

2

2

n1-03

Hunting Prevention Time Constant

ms

100

100

n1-16

Hunting Prevention High Fc Gain

-

0.50

0.50

n5-02

Motor Inertia Acceleration Time

s

2.857

3.333

1

Parameters in parentheses are for motor 2.

2

The display units are different for different models: The units are Ω for models 2004 to 2415, 4002 to 4675 and mΩ for models 4810 to 4H12.

3

The display units are different for different models: The units are Ω for models 2004 to 2415, 4002 to 4675 and mΩ for models 4810 to 4H12.