CALL
|
Serial Comm Transmission Error
|
The communications cable wiring is incorrect.
|
Correct wiring errors.
|
|
There is a short circuit in the communications cable or the communications cable is not connected.
|
|
|
A programming error occurred on the controller side.
|
Examine communications at start-up and correct programming errors.
|
|
There is damage to the communications circuitry.
|
-
Do a self-diagnostics check.
-
If the problem continues, replace the control board or the drive. Contact Yaskawa or your nearest sales representative to replace the control board.
|
|
The termination resistor setting for MEMOBUS/Modbus communications is incorrect.
|
On the last drive in a MEMOBUS/Modbus network, set DIP switch S2 to the ON position to enable the termination resistor.
|
Note:
-
The drive detects this error if it does not correctly receive control data from the controller when energizing the drive.
-
If the drive detects this error, the terminal assigned to H2-01 to H2-04 = 10 [MFDO Function Select = Alarm] will activate.
|