0
|
During Run
|
0: During Run
|
|
1
|
Zero Speed
|
1: Zero Speed
|
|
2
|
Speed Agree 1
|
2: Speed Agree 1
|
|
3
|
User-Set Speed Agree 1
|
3: User-Set Speed Agree 1
|
|
4
|
Frequency Detection 1
|
4: Frequency Detection 1
|
|
5
|
Frequency Detection 2
|
5: Frequency Detection 2
|
|
6
|
Drive Ready
|
6: Drive Ready
|
|
7
|
DC Bus Undervoltage
|
7: DC Bus Undervoltage
|
|
8
|
During Baseblock (N.O.)
|
8: During Baseblock (N.O.)
|
|
9
|
Frequency Reference from Keypad
|
9: Frequency Reference from Keypad
|
|
A
|
Run Command Source
|
A: Run Command from Keypad
|
|
B
|
Torque Detection 1 (N.O.)
|
B: Torque Detection 1 (N.O.)
|
|
C
|
Frequency Reference Loss
|
C: Frequency Reference Loss
|
|
D
|
Braking Resistor Fault
|
D: Braking Resistor Fault
|
|
E
|
Fault
|
E: Fault
|
|
F 1
|
Not Used
|
F: Not Used
|
|
10
|
Alarm
|
10: Alarm
|
|
11
|
Fault Reset Command Active
|
11: Fault Reset Command Active
|
|
12
|
Timer Output
|
12: Timer Output
|
|
13
|
Speed Agree 2
|
13: Speed Agree 2
|
|
14
|
User-Set Speed Agree 2
|
14: User-Set Speed Agree 2
|
|
15
|
Frequency Detection 3
|
15: Frequency Detection 3
|
|
16
|
Frequency Detection 4
|
16: Frequency Detection 4
|
|
17
|
Torque Detection 1 (N.C.)
|
17: Torque Detection 1 (N.C.)
|
|
18
|
Torque Detection 2 (N.O.)
|
18: Torque Detection 2 (N.O.)
|
|
19
|
Torque Detection 2 (N.C.)
|
19: Torque Detection 2 (N.C.)
|
|
1A
|
During Reverse
|
1A: During Reverse
|
|
1B
|
During Baseblock (N.C.)
|
1B: During Baseblock (N.C.)
|
|
1C
|
Motor 2 Selected
|
1C: Motor 2 Selected
|
|
1D
|
During Regeneration
|
1D: During Regeneration
|
|
1E
|
Executing Auto-Restart
|
1E: Executing Auto-Restart
|
|
1F
|
Motor Overload Alarm (oL1)
|
1F: Motor Overload Alarm (oL1)
|
|
20
|
Drive Overheat Pre-Alarm (oH)
|
20: Drive Overheat Pre-Alarm (oH)
|
|
21
|
Safety Monitor Output Status
|
21: Safe Torque OFF
|
|
22
|
Mechanical Weakening Detection
|
22: Mechanical Weakening Detection
|
|
2F
|
Maintenance Notification
|
2F: Maintenance Notification
|
|
30
|
During Torque Limit
|
30: During Torque Limit
|
|
31
|
During Speed Limit
|
31: During Speed Limit
|
|
32
|
In Speed Limit During Trq Ctrl
|
32: In Speed Limit During Trq Ctrl
|
|
33
|
Zero Servo Complete
|
33: Zero Servo Complete
|
|
37
|
During Frequency Output
|
37: During Frequency Output
|
|
38
|
Drive Enabled
|
38: Drive Enabled
|
|
39
|
Watt Hour Pulse Output
|
39: Watt Hour Pulse Output
|
|
3C
|
LOCAL Control Selected
|
3C: LOCAL Control Selected
|
|
3D
|
During Speed Search
|
3D: During Speed Search
|
|
3E
|
PID Feedback Low
|
3E: PID Feedback Low
|
|
3F
|
PID Feedback High
|
3F: PID Feedback High
|
|
4A
|
During KEB Ride-Thru
|
4A: During KEB Ride-Thru
|
|
4B
|
During Short Circuit Braking
|
4B: During Short Circuit Braking
|
|
4C
|
During Fast Stop
|
4C: During Fast Stop
|
|
4D
|
oH Pre-Alarm Time Limit
|
4D: oH Pre-Alarm Time Limit
|
|
4E 2
|
Braking Transistor Fault (rr)
|
4E: Braking Transistor Fault (rr)
|
|
4F 2
|
Braking Resistor Overheat (rH)
|
4F: Braking Resistor Overheat (rH)
|
|
60
|
Internal Cooling Fan Alarm
|
60: Internal Cooling Fan Failure
|
|
61
|
Pole Position Detection Complete
|
61: Pole Position Detection Complete
|
|
62
|
Modbus Reg 1 Status Satisfied
|
62: Modbus Reg 1 Status Satisfied
|
|
63
|
Modbus Reg 2 Status Satisfied
|
63: Modbus Reg 2 Status Satisfied
|
|
65
|
Standby Output
|
65: Standby Output
|
|
66
|
Comparator1
|
66: Comparator1
|
|
67
|
Comparator2
|
67: Comparator2
|
|
69
|
External Power 24V Supply
|
69: External Power 24V Supply
|
|
6A
|
Data Logger Error
|
6A: Data Logger Error
|
|
90 - 93
|
DWEZ Digital Output 1 to 4
|
90 to 93: DWEZ Digital Outputs 1 to 4
|
|
A0 - A7
|
DWEZ Extended Digital Outputs 1 to 8
|
A0 to A7: DWEZ Extended Digital Outputs 1 to 8
|
|
100 - 1A7
|
Inverse output of 0 to A7
Sets an inverse output of the function for the MFDO. Put a 1 at the front of the function setting to set inverse output. For example, set 138 for inverse output of 38 [Drive Enabled].
|
100 to 1A7: Inverse Outputs of 0 to A7
|