YASKAWA AC Drive GA700 High Performance Type Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C6-01
(0223)
Normal / Heavy Duty Selection
Sets the drive duty rating.
The overload tolerance is 150% of the rated output current for 60 seconds.
The overload tolerance is 110% of the rated output current for 60 seconds.
0
(0, 1)
Details
C6-02
(0224)
Carrier Frequency Selection
Sets the carrier frequency for the transistors in the drive.
Use C6-03 to C6-05 to set detailed setting values.
The carrier frequency for Swing PWM 1 to 4 is equivalent to 2.0 kHz.
Determined by A1-02, C6-01, and o2-04
(Determined by A1-02)
C6-03
(0225)
Carrier Frequency Upper Limit
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User Defined (C6-03 to C6-05)] to set this parameter.
Determined by C6-02
(1.0 - 15.0 kHz)
C6-04
(0226)
Carrier Frequency Lower Limit
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User Defined (C6-03 to C6-05)] to set this parameter.
C6-05
(0227)
Carrier Freq Proportional Gain
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User Defined (C6-03 to C6-05)] to set this parameter.
(0 - 99)
C6-09
(022B)
Carrier Freq at Rotational Tune
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
When A1-02 = 5, 6, 7 [Control Method Selection = OLV/PM, AOLV/PM, CLV/PM], the carrier frequency is 2 kHz.
When A1-02 = 5, 6, 7 [Control Method Selection = OLV/PM, AOLV/PM, CLV/PM], the carrier frequency is as specified in C6-02.