No. (Hex.) Name Description Default (Range) Ref. F2-01 (038F) Analog Input Function Selection Sets the input method for the analog reference used with AI-A3. 0 3 Independent Channels You can input the MFAI signal from terminals V1 through V3 for AI-A3. The functions for terminals A1, A2, and A3 on the drive are sent to terminals V1, V2, and V3 for AI-A3. Use gain and bias adjustment when you input current to set signals to have negative numbers. 1 3 Channels Added Together You can input the frequency reference directly. The sum value when you add the input from terminals V1 to V3 becomes the frequency reference. 0 (0, 1) Details No. (Hex.) Name Description Default (Range) Ref. F2-02 (0368) RUN Analog Input Option Card Gain Sets the analog reference gain as a percentage when the maximum output frequency is 100%. Note: Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to enable this function. Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency. A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency] A1-02 = 8: E9-02 [Maximum Speed] 100.0% (-999.9 - +999.9%) Details No. (Hex.) Name Description Default (Range) Ref. F2-03 (0369) RUN Analog Input Option Card Bias Sets the analog reference bias as a percentage when the maximum output frequency is 100%. Note: Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to enable this function. Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency. A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency] A1-02 = 8: E9-02 [Maximum Speed] 0.0% (-999.9 - +999.9%) Details