No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F2-01

(038F)

Analog Input Function Selection

Sets the input method for the analog reference used with AI-A3.

0
3 Independent Channels

You can input the MFAI signal from terminals V1 through V3 for AI-A3. The functions for terminals A1, A2, and A3 on the drive are sent to terminals V1, V2, and V3 for AI-A3. Use gain and bias adjustment when you input current to set signals to have negative numbers.

1
3 Channels Added Together

You can input the frequency reference directly. The sum value when you add the input from terminals V1 to V3 becomes the frequency reference.

0

(0, 1)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F2-02

(0368)

RUN

Analog Input Option Card Gain

Sets the analog reference gain as a percentage when the maximum output frequency is 100%.

Note:
  • Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to enable this function.

  • Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

    • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

    • A1-02 = 8: E9-02 [Maximum Speed]

100.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

F2-03

(0369)

RUN

Analog Input Option Card Bias

Sets the analog reference bias as a percentage when the maximum output frequency is 100%.

Note:
  • Set F2-01 = 1 [Analog Input Function Selection = 3 Channels Added Together] to enable this function.

  • Parameter A1-02 [Control Method Selection] selects which parameter is the maximum output frequency.

    • A1-02 ≠ 8 [EZOLV]: E1-04 [Maximum Output Frequency]

    • A1-02 = 8: E9-02 [Maximum Speed]

0.0%

(-999.9 - +999.9%)

Details