Do these steps for a no-load test run:

  1. Energize the drive, or push [F2 Key] to show the HOME screen.

    If [Home] is not shown on [F2 Key], push [F1 Key] (Back) to show [Home] on [F2 Key].

  2. Push [LO/RE selection key] to illuminate the LOCAL/REMOTE indicator.
  3. Push [ENTER Key] to show d1-01 [Reference 1], and set it to 6.00 Hz.
  4. Push [RUN key].

    The RUN indicator illuminates, and the motor runs at 6.00 Hz in the forward direction.

  5. Make sure that the motor is rotating in the correct direction and that the drive does not show a fault.

    If the drive detects a fault, remove the cause.

    • Forward Rotation of Motor (Counter Clockwise Direction as Seen from Load Shaft)
  6. Push [Up arrow key] to increase the frequency reference value.

    Change the setting value in increments of 10 Hz if necessary and examine the response.

  7. Each time you increase the setting value, use U1-03 [Output Current] to check the drive output current.

    When the output current of the drive is not more than the motor rated current, the status is correct.

    Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz

  8. Make sure that the motor rotates correctly, then push [STOP key].

    The RUN indicator will flash. When the motor stops, the indicator will go out.