LT-1
|
Cooling Fan Maintenance Time
|
The cooling fan is at 90% of its expected performance life.
|
Replace the cooling fan, then set o4-03 = 0 [Fan Operation Time Setting = 0 h] to reset the cooling fan operation time.
|
2F
|
|
LT-2
|
Capacitor Maintenance Time
|
The capacitors for the main circuit and control circuit are at 90% of expected performance life.
|
Replace the board or the drive.
Contact Yaskawa or your nearest sales representative to replace the board.
|
|
LT-3
|
SoftChargeBypassRelay MainteTime
|
The soft charge bypass relay is at 90% of its performance life estimate.
|
Replace the board or the drive.
Contact Yaskawa or your nearest sales representative to replace the board.
|
|
LT-4
|
IGBT Maintenance Time (50%)
|
The IGBT is at 50% of its expected performance life.
|
Check the load, carrier frequency, and output frequency.
|
|
TrPC
|
IGBT Maintenance Time (90%)
|
The IGBT is at 90% of its expected performance life.
|
Replace the IGBT or the drive.
|