No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-01

(041D)

Terminal FM Analog Output Select

Sets the monitoring number (Ux-xx) to be output from MFAO terminal FM.

Note:

Set the x-xx part of the Ux-xx [Monitors]. For example, set H4-01 = 102 to monitor U1-02 [Output Frequency].

If the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set H4-01 = 1301 to monitor Ud-01.

102

(000 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-02

(041E)

RUN

Terminal FM Analog Output Gain

Sets the gain of the monitor signal that is sent from MFAO terminal FM.

Sets the analog signal output level from the terminal FM at 10 V or 20 mA as 100% when an output for monitoring items is 100%.

100.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-03

(041F)

RUN

Terminal FM Analog Output Bias

Sets the bias of the monitor signal that is sent from MFAO terminal FM.

Set the level of the analog signal sent from terminal FM at 10 V or 20 mA as 100% when an output for monitoring items is 0%.

0.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-04

(0420)

Terminal AM Analog Output Select

Sets the monitoring number (Ux-xx) to be output from MFAO terminal AM.

Note:

Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-04 = 103 to monitor U1-03 [Output Current].

If the x part of Ux is a letter, replace the letter (hexadecimal number) with a decimal number. For example, set H4-04 = 1301 to monitor Ud-01.

103

(000 - 9999)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-05

(0421)

RUN

Terminal AM Analog Output Gain

Sets the gain of the monitor signal that is sent from MFAO terminal AM.

When an output for monitoring items is 0%, this parameter sets the analog signal output level from the AM terminal at 10 V or 20 mA as 100%.

50.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-06

(0422)

RUN

Terminal AM Analog Output Bias

Sets the bias of the monitor signal that is sent from MFAO terminal AM.

When an output for monitoring items is 0%, this parameter sets the analog signal output level from the AM terminal at 10 V or 20 mA as 0%.

0.0%

(-999.9 - +999.9%)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-07

(0423)

Terminal FM Signal Level Select

Sets the MFAO terminal FM output signal level.

Note:

Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.

0
0-10V (Lower Limit at 0)
 
1
-10 to +10V (Bipolar Reference)
 
2
4 to 20 mA
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-08

(0424)

Terminal AM Signal Level Select

Sets the MFAO terminal AM output signal level.

Note:

Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.

0
0 to 10 Vdc
 
1
-10 to +10 Vdc
 
2
4 to 20 mA
 

0

(0 - 2)

Details

No.

(Hex.)

Name

Description

Default

(Range)

Ref.

H4-20

(0B53)

Analog Power Monitor 100% Level

Sets the level at 10 V when U1-08 [Output Power] is set for analog output.

Note:

On drive models 2xxx, and 4002 to 4675, the setting unit is 0.01 kW. The setting range is 0.00 kW to 650.00 kW.

On drive models 4810 to 4H12, the setting unit is 0.1 kW. The setting range is 0.0 kW to 1000.0 kW.

0.00 kW

(0.00 - 1000.0 kW)

Details