The Safe Disable input provides the stop function that complies with “Safe Torque Off” as specified by IEC/EN 61800-5-2. The Safe Disable input meets the requirements of EN ISO 13849-1 and IEC/EN 61508. It also has a safety status monitor to detect safety circuit errors.
When you install the drive as a component in a system, you must make sure that the system complies with the applicable safety standards.
Refer to Table 1 for safety function specifications.
Table 1. Safe Disable Specifications
|
Item
|
Description
|
|
Input/Output
|
-
Input: 2
Safe Disable input (H1, H2)
Signal ON level: 18 Vdc to 28 Vdc
Signal OFF level: -4 Vdc to +4 Vdc
-
Output: 1
MFDO safety monitor output for external device monitor (EDM)
|
|
Response time from when the input opens to when the drive output stops
|
3 ms or less
|
|
Response time from when the H1 and H2 terminal inputs open to when the EDM signal operates
|
20 ms or less
|
|
Failure probability
|
Less frequent operation request mode
|
PFD = 4.65E-6
|
|
Frequent operation request mode or continuous mode
|
PFH = 1.11E-9
|
|
Performance level
|
The Safe Disable input complies with the performance level requirements of EN ISO 13849-1.
|
|
HFT (hardware fault tolerance)
|
N = 1
|
|
Type of subsystem
|
Type B
|
Note:
EDM = External Device Monitoring
PFD = Probability of Failure on Demand
PFH = Probability of Dangerous Failure per Hour