CE Standards Compliance for DC Power Supply Input

To comply with CE Standards, install a fuse for the DC power supply input.

Figure 1 shows a wiring example for a DC power supply that has two drives connected in parallel.

Figure 1. Wiring Example for DC Power Supply Input
Note:
  • On models 4810 to 4H12, use DC power supply input terminals +1 and - to connect a PWM converter that can do protection coordination on the input side, for example a Yaskawa D1000-series Power Regenerative Converter. You cannot use a DC power supply to connect drives in parallel.

  • Install a fuse for each drive when operating more than one drive. If one fuse blows, replace all fuses.

  • Install the external filter (system) to comply with the EMC Directive.

Refer toTable 1 and Table 2 for the recommended fuses.

Table 1. Recommended Fuse (Three-Phase 200 V Class)

Drive Model

Fuse

Manufacturer: Bussmann

Model

Qty

2004

FWH-45B

2

2006

FWH-45B

2

2008

FWH-45B

2

2010

FWH-45B

2

2012

FWH-50B

2

2018

FWH-80B

2

2021

FWH-80B

2

2030

FWH-125B

2

2042

FWH-150B

2

2056

FWH-200B

2

2070

FWH-250A

2

2082

FWH-250A

FWH-300A1

2

2110

FWH-250A

FWH-275A1

2

2138

FWH-300A

FWH-350A1

2

2169

FWH-350A

FWH-450A1

2

2211

FWH-450A

FWH-600A1

2

2257

FWH-600A

FWH-700A1

2

2313

FWH-800A

FWH-1000B1

2

2360

FWH-1000B

2

2415

FWH-1000B

2

 
Table 2. Recommended Fuse (Three-Phase 400 V Class)

Drive Model

Fuse

Manufacturer: Bussmann

Model

Qty

4002

FWH-50B

2

4004

FWH-50B

2

4005

FWH-50B

2

4007

FWH-60B

2

4009

FWH-60B

2

4012

FWH-60B

2

4018

FWH-80B

2

4023

FWH-90B

2

4031

FWH-150B

2

4038

FWH-200B

2

4044

FWH-200B

2

4060

FWH-225A

2

4075

FWH-250A

2

4089

FWH-275A

2

4103

FWH-275A

2

4140

FWH-300A

FWH-325A1

2

4168

FWH-400A

FWH-450A1

2

4208

FWH-500A

FWH-600A1

2

4250

FWH-600A

FWH-700A1

2

4296

FWH-700A

FWH-800A1

2

4371

FWH-800A

FWH-1000B1

2

4389

FWH-1000B

FWH-1200B1

2

4453

FWH-1200B

FWH-1400A1

2

4568

FWH-1200B

FWH-1600A1

2

4675

FWH-1600A

2

4810

-2

-

4930

-2

-

4H11

-2

-

4H12

-2

-

 
1

Yaskawa recommends a fuse with a large rated current for applications with repeated loads.

2

It is not necessary to install fuses. On models 4810 to 4H12, use DC power supply input terminals +1 and - to connect a PWM converter that can do protection coordination on the input side, for example a Yaskawa D1000-series Power Regenerative Converter.