No.

(Hex.)

Name

Description

Default

(Range)

E5-03

(032B)

Motor Rated Current (FLA)

Sets the PM motor rated current (FLA).

Determined by E5-01

(10% to 200% of the drive rated current)

Note:

The display units are different for different models:

  • 0.01 A: models 2004 - 2042, 4002 - 4023

  • 0.1 A: models 2056 - 2415, 4031 - 4H12

The drive automatically sets E5-03 to the value input for “PM Motor Rated Current” after you do these types of Auto-Tuning:

  • Manual Entry w/ Motor Data Sheet

  • PM Stationary Auto-Tuning

  • Stationary (R Only)

  • Rotational (Ld, Lq, R, back-EMF)