No. (Hex.) Name Description Default (Range) L1-03 (0482) Motor Thermistor oH Alarm Select Sets drive operation when the PTC input signal entered into the drive is at the oH3 [Motor Overheat Alarm] detection level. 3 (0 - 3) 0 Ramp to Stop The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF. 1 Coast to Stop The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF. 2 Fast Stop (Use C1-09) The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC turns ON, and MB-MC turns OFF. 3 Alarm Only The keypad shows oH3 and the drive continues operation. The output terminal set for Alarm [H2-01 to H2-04 = 10] activates.