Broadcast messages are available as read-only.

The undefined bit signal in the broadcast operation signal uses the local data signal.

Table 1. Broadcast Messages for MEMOBUS/Modbus Communication

Register No. (Hex.)

Description

0001

Operation signal

bit 0

Run command

1: Run, 0: Stop

bit 1

Reverse run command

1: Reverse, 0: Forward run

bit 2 - 3

Reserved

bit 4

External fault

1: EF0 [Option Card External Fault]

bit 5

Fault Reset

1: Reset command

bit 6 - B

Reserved

bit C

MFDI terminal S5 input

bit D

MFDI terminal S6 input

bit E

MFDI terminal S7 input

bit F

MFDI terminal S8 input

0002

Frequency reference

30000/100%