Reverse the removal procedure for fan installation.

  1. Align the pin on the fan unit base with the notch on the fan and put the circuit board cooling fan in the fan unit, then use the screws to safety the circuit board cooling fan to the fan unit base.

    Tighten the screws to a correct tightening torque:

    • 0.98 N∙m to 1.33 N∙m (8.67 lbf∙in to 11.77 lbf∙in)

    Note:

    Make sure that you do not pinch cables between the circuit board cooling fan and the fan unit base.

    Figure 1. Install the Circuit Board Cooling Fan
    • Circuit board cooling fan
    • Fan unit base
    • Alignment pin on fan unit base
  2. Put the circuit board cooling fan unit into the specified location and slide it down, then use the screws to safety it to the drive.

    Tighten the screws to a correct tightening torque:

    • 0.98 N∙m to 1.33 N∙m (8.67 lbf∙in to 11.77 lbf∙in)

    Figure 2. Install the Circuit Board Cooling Fan Unit
  3. Connect the fan cable to the fan connectors.
    Figure 3. Fan Connect Cooling Fan Connectors
    • Fan connectors
    • Fan cable
    • Circuit board cooling fan units
  4. Install the drive cover.
  5. Energize the drive and set o4-03 = 0 [Fan Operation Time Setting = 0 h] to reset the fan operation time.