YASKAWA AC Drive GA700 High Performance Type Technical Manual
Model
Terminal
Recomm. Gauge
mm2
Applicable Gauge
(IP20 Applicable Gauge 1)
Wire Stripping Length2
mm
Terminal Screw
Size and Shape
Tightening Torque
N∙m (lbf∙in)
2004
R/L1, S/L2, T/L3
2.5
2.5 - 10
(2.5 - 10)
10
M4
1.5 - 1.7
(13.5 - 15)
U/T1, V/T2, W/T3
-, +1, +2
2.5 - 16
(2.5 - 16)
18
M5
2.3 - 2.5
(19.8 - 22)
B1, B2
2.5 - 4
(2.5 - 4)
(-)
-
1.2 - 1.5
(10.6 - 13.3)
2006
2008
2010
2012
2018
4
2021
6
4 - 10
2030
6 - 10
2.0 - 2.5
(17.7 - 22.1)
2042
16
2056
25
2.5 - 25
(10 - 25)
(6 - 16)
35
2.5 - 35
(10 - 35)
20
M6
5 - 5.5
(45 - 49)
10 - 16
5.4 - 6.0
(47.8 - 53.1)
2070
(25 - 35)
(16)
50
2.5 - 50
(35 - 50)
16 - 25
2082
(16 - 25)
2110
16 - 35
27
8 - 9
(71 - 80)
-, +1
25 - 50
(25 - 50)
M8
10 - 12
(89 - 107)
6 - 25
(6 - 25)
21
3 - 3.5
(27 - 31)
2138
16 - 50
(50)
70
25 - 70
(50 - 70)
6 - 35
(6 - 35)
2169
50 - 95
(95)
37
M10
12 - 14
(107 - 124)
-, -, +1, +1 34
28
+3 4
9.0 - 11
(79.7 - 97.4)
2211
95
+34
2257
50 × 2P
25 - 95 × 2P
(70 - 95 × 2P)
(177)
70 × 2P
35 - 120 × 2P
(120 × 2P)
+3
35 × 2P
25 - 70 × 2P
(70 × 2P)
95 - 240
18 - 23
(159 - 204)
2313
95 × 2P
2360
120 × 2P
70 - 150 × 2P
(150 × 2P)
M12
(310)
95 - 185 × 2P
(185 × 2P)
50 - 95 × 2P
120
120 - 240
32 - 40
(283 - 354)
2415
For IP20 protection, use wires that are in the range of applicable gauges.
Remove insulation from the ends of wires to expose the length of wire shown.
Terminals - and +1 have two screws. The Recommended Gauge is the wire gauge for one terminal.
A junction terminal is necessary to connect a braking unit (CDBR-series) to terminals - and +3.