When you install drives horizontally, set L8-12 = 40 [Ambient Temperature Setting = 40 °C] and L8-35 = 1 [Installation Method Selection = Side-by-Side Mounting]. Use the clearances specified in Figure 2 and Figure 3 to install the drive. Make sure that there is sufficient space for wiring and airflow. To install the drive models B001 - B012, 2001 - 2021, and 4001 - 4012 horizontally, install an external cooling fan. Refer to Table 1 for more information about the external cooling fan.
Figure 1. Airflow Direction of Horizontal installation
Figure 2. Installation Clearances for Horizontal Installation: B001 - B012, 2001 - 2021, and 4001 - 4012
- 50 mm (2 in) minimum
- 30 mm (1.18 in) minimum on each side
- 100 mm (3.94 in) minimum below
- Airflow direction
- External cooling fan
- 30 mm (1.18 in) between the drive and the external cooling fan
- 120 mm (4.72 in) minimum between the external cooling fan and the enclosure panel
- Heatsink height
Figure 3. Installation Clearances for Horizontal Installation: B018, 2030 - 2082, and 4018 - 4060
- 50 mm (2 in) minimum
- 30 mm (1.18 in) minimum on each side
- 100 mm (3.94 in) minimum above and below
- Airflow direction
Table 1. Specifications of External Cooling Fan for Horizontal (Floor) Installation
|
Model
|
Airflow
(m3/min)
|
Static Pressure
(Pa)
|
|
B001 - B004
2001 - 2006
|
0.18 minimum
|
63.7 minimum
|
|
B006 - B012
2008 - 2021
4001 - 4012
|
1.11 minimum
|
244 minimum
|
|
B018
2030 - 2082
4018 - 4060
|
External cooling fan is not necessary
|