Set the signal type for terminals AM and FM to voltage or current output. Use jumper switch S5 and H4-07, H4-08 [Terminal FM Signal Level Select, Terminal AM Signal Level Select] to set the signal type.

Figure 1. Location of Jumper Switch S5 (Photocoupler Output/Screw Clamp Terminal Board Type)
Figure 2. Location of Jumper Switch S5 (Relay Output/Screw Clamp Terminal Board Type)
 

Terminal

Types of Output Signals

Jumper Switch S5

Parameter

No.

Signal Level

FM

Voltage output

(Default)

H4-07

0: 0 V to 10 V

1: -10 V to +10 V

Current output

2: 4 mA to 20 mA

AM

Voltage output

(Default)

H4-08

0: 0 V to 10 V

1: -10 V to +10 V

Current output

2: 4 mA to 20 mA