Set the signal type for terminals AM and FM to voltage or current output. Use jumper switch S5 and H4-07, H4-08 [Terminal FM Signal Level Select, Terminal AM Signal Level Select] to set the signal type.
Figure 1. Location of Jumper Switch S5 (Photocoupler Output/Screw Clamp Terminal Board Type)
Figure 2. Location of Jumper Switch S5 (Relay Output/Screw Clamp Terminal Board Type)
|
Terminal
|
Types of Output Signals
|
Jumper Switch S5
|
Parameter
|
|
No.
|
Signal Level
|
|
FM
|
Voltage output
(Default)
|
|
H4-07
|
0: 0 V to 10 V
1: -10 V to +10 V
|
|
Current output
|
|
2: 4 mA to 20 mA
|
|
AM
|
Voltage output
(Default)
|
|
H4-08
|
0: 0 V to 10 V
1: -10 V to +10 V
|
|
Current output
|
|
2: 4 mA to 20 mA
|