Jump to main content

Rated Output Current

Table 1 , Table 2, and Table 3 give the rated output current values.

Note:
  • Rated output current values are applicable for drives that operate at standard specifications.

  • Derate the output current in applications that:

    • Increase the carrier frequency

    • Have high ambient temperature

    • Install drives side-by-side.

  • Use C6-01 [Normal / Heavy Duty Selection] to select Normal Duty rating (ND) or Heavy Duty rating (HD).

Table 1. Single-Phase AC 200 V Class

Model

Heavy Duty Rating (HD)

[C6-01 = 0]

Normal Duty Rating (ND)

[C6-01 = 1]

(Default)

Maximum Applicable Motor Output

kW (HP)

Rated Output Current

A

Maximum Applicable Motor Output

kW (HP)

Rated Output Current

A

B001

0.1 (1/6)

0.8

0.2 (1/6)

1.2

B002

0.2 (1/4)

1.6

0.4 (1/4)

1.9

B004

0.4 (1/2)

3.0

0.75 (3/4)

3.5

B006

0.75 (1)

5.0

1.1 (1.5)

6.0

B010

1.5 (2)

8.0

2.2 (3)

9.6

B012

2.2 (3)

11.0

3.0 (3)

12.2

B018

3.7 (5)

17.6

-

-

Table 2. Three-Phase AC 200 V Class

Model

Heavy Duty Rating (HD)

[C6-01 = 0]

Normal Duty Rating (ND)

[C6-01 = 1]

(Default)

Maximum Applicable Motor Output

kW (HP)

Rated Output Current

A

Maximum Applicable Motor Output

kW (HP)

Rated Output Current

A

2001

0.1 (1/6)

0.8

0.2 (1/6)

1.2

2002

0.2 (1/4)

1.6

0.4 (1/4)

1.9

2004

0.4 (1/2)

3.0

0.75 (3/4)

3.5

2006

0.75 (1)

5.0

1.1 (1.5)

6.0

2008

1.1 (1.5)

6.9

1.5 (2)

8.0

2010

1.5 (2)

8.0

2.2 (3)

9.6

2012

2.2 (3)

11.0

3.0 (4)

12.2

2018

3.0 (4)

14.0

3.7 (5)

17.5

2021

3.7 (5)

17.6

5.5 (7.5)

21.0

2030

5.5 (7.5)

25.0

7.5 (10)

30.0

2042

7.5 (10)

33.0

11.0 (15)

42.0

2056

11.0 (15)

47.0

15.0 (20)

56.0

2070

15.0 (20)

60.0

18.5 (25)

70.0

2082

18.5 (25)

75.0

22.0 (30)

82.0

Table 3. Three-Phase AC 400 V Class

Model

Heavy Duty Rating (HD)

[C6-01 = 0]

Normal Duty Rating (ND)

[C6-01 = 1]

(Default)

Maximum Applicable Motor Output

kW (HP)

Rated Output Current

A

Maximum Applicable Motor Output

kW (HP)

Rated Output Current

A

4001

0.2 (1/2)

1.2

0.4 (1/2)

1.2

4002

0.4 (3/4)

1.8

0.75 (1)

2.1

4004

0.75 (2)

3.4

1.5 (2)

4.1

4005

1.5 (3)

4.8

2.2 (3)

5.4

4007

2.2 (3)

5.6

3.0 (4)

7.1

4009

3.0 (4)

7.3

3.7 (5)

8.9

4012

3.7 (5)

9.2

5.5 (7.5)

11.9

4018

5.5 (10)

14.8

7.5 (10)

17.5

4023

7.5 (10)

18.0

11.0 (15)

23.4

4031

11.0 (15)

24.0

15.0 (20)

31.0

4038

15.0 (20)

31.0

18.5 (25)

38.0

4044

18.5 (25)

39.0

22.0 (30)

44.0

4060

22.0 (30)

45.0

30.0 (40)

60.0