Jump to main content

Single-Phase 200 V Class

Table 1. Drive Watt Loss (HD, Fc = 2 kHz)

Model

The rated output current

A

Carrier Frequency

kHz

Interior Unit Loss

W

Cooling Fin Loss

W

Total Loss

W

B001

0.8

2

7

4

11

B002

1.6

2

10

7

17

B004

3

2

13

13

26

B006

5

2

17

23

40

B010

8

2

30

37

67

B012

11

2

40

48

88

B018 1

17.6

2

49

72

121

 
Table 2. Drive Watt Loss (HD, Fc = Default Setting)

Model

The rated output current

A

Carrier Frequency

kHz

Interior Unit Loss

W

Cooling Fin Loss

W

Total Loss

W

B001

0.8

10

8

5

13

B002

1.6

10

10

9

19

B004

3

10

14

16

30

B006

5

10

18

28

46

B010

8

8

31

42

73

B012

11

8

41

55

96

B018 1

17.6

8

53

98

151

Table 3. Drive Watt Loss (ND)

Model

The rated output current

A

Carrier Frequency

kHz

Interior Unit Loss

W

Cooling Fin Loss

W

Total Loss

W

B001

1.2

2

8

6

14

B002

1.9

2

14

11

25

B004

3.5

2

14

17

31

B006

6.0

2

17

26

43

B010

9.6

2

36

50

86

B012

12.2

2

48

60

108

B018 1

-

2

49

92

141