Model Specifications (Three-Phase 200 V Class)

Table 1. Ratings (Three-Phase 200 V Class)

Model

2001

2002

2004

2006

Maximum Applicable Motor Output (kW)

HD 1

0.1

0.2

0.2

0.75

ND 2

0.2

0.4

0.75

1.1

Maximum Applicable Motor Output (HP)

HD 1

1/6

1/4

1/2

1

ND 2

1/6

1/4

3/4

1.5

Input

Rated Input Current (A)

HD (AC)

0.7

1.5

2.9

5.8

HD (DC)

0.9

1.8

3.6

7.1

ND (AC)

1.1

1.9

3.9

7.3

ND (DC)

1.3

2.3

4.8

8.9

Output

Rated Output Capacity (kVA) 3

HD

0.3

0.6

1.1

1.9

ND

0.5

0.7

1.3

2.3

Rated Output Current (A)

HD

0.8

1.6

3.0

5.0

ND

1.2

1.9

3.5

6

Overload Tolerance

  • HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

  • ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

Note:

Derating can be necessary for applications that start and stop frequently.

Carrier Frequency

HD: 10 kHz without derating the drive capacity.

ND: 2 kHz without derating the drive capacity.

Derate the drive capacity to use values to 15 kHz maximum.

Maximum Output Voltage

Three-phase 200 V to 240 V

Note:

The maximum output voltage is proportional to the input voltage.

Maximum Output Frequency

  • EZOLV: 120 Hz

  • AOLV/PM: 270 Hz

  • V/f, OLV, OLV/PM: 590 Hz

Measures for Harmonics

DC reactor

External options

Braking Device

Braking Transistor

Standard internal characteristics

EMC Filter

EMC Filter

IEC61800-3

Factory option

Models 2xxxE: Category C3 (Conducted emission)

Power Supply

Rated Voltage/Rated Frequency

  • Three-phase AC power supply 200 V to 240 V at 50/60 Hz

  • DC power supply 270 V to 340 V

Permitted Voltage Fluctuation

-15% to +10%

Permitted Frequency Fluctuation

±5%

Input Power (kVA)

HD

0.3

0.7

1.3

2.7

ND

0.5

1.2

1.8

3.3

 
Table 2. Ratings (Three-Phase 200 V Class)

Model

2008

2010

2012

2018

Maximum Applicable Motor Output (kW)

HD 1

1.1

1.5

2.2

3

ND 2

1.5

2.2

3

3.7

Maximum Applicable Motor Output (HP)

HD 1

1.5

2

3

4

ND 2

2

3

4

5

Input

Rated Input Current (A)

HD (AC)

7.0

7.5

11

15.6

HD (DC)

8.6

9.2

13.5

19.1

ND (AC)

8.8

10.8

13.9

18.5

ND (DC)

10.8

13.2

17

22.7

Output

Rated Output Capacity (kVA) 3

HD

2.6

3

4.2

5.3

ND

3

3.7

4.6

6.7

Rated Output Current (A)

HD

6.9

8.0

11.0

14.0

ND

8.0

9.6

12.2

17.5

Overload Tolerance

  • HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

  • ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

Note:

Derating can be necessary for applications that start and stop frequently.

Carrier Frequency

HD: 8 kHz without derating the drive capacity.

ND: 2 kHz without derating the drive capacity.

Derate the drive capacity to use values to 15 kHz maximum.

Maximum Output Voltage

Three-phase 200 V to 240 V

Note:

The maximum output voltage is proportional to the input voltage.

Maximum Output Frequency

  • V/f, OLV, OLV/PM: 590 Hz

  • AOLV/PM: 270 Hz

  • EZOLV: 120 Hz

Measures for Harmonics

DC reactor

External options

Braking Device

Braking Transistor

Standard internal characteristics

EMC Filter

EMC Filter

IEC61800-3

Factory option

Models 2xxxE: Category C3 (Conducted emission)

Power Supply

Rated Voltage/Rated Frequency

  • Three-phase AC power supply 200 V to 240 V at 50/60 Hz

  • DC power supply 270 V to 340 V

Permitted Voltage Fluctuation

-15% to +10%

Permitted Frequency Fluctuation

±5%

Input Power (kVA)

HD

3.2

3.4

5.0

7.1

ND

4.0

4.9

6.4

8.5

Table 3. Ratings (Three-Phase 200 V Class)

Model

2021

2030

2042

2056

Maximum Applicable Motor Output (kW)

HD 1

3.7

5.5

7.5

11

ND 2

5.5

7.5

11

15

Maximum Applicable Motor Output (HP)

HD 1

5

7.5

10

15

ND 2

7.5

10

15

20

Input

Rated Input Current (A)

HD (AC)

18.9

24

37

52

HD (DC)

23.1

29.4

45.3

63.7

ND (AC)

24

37

52

68

ND (DC)

29.4

45.3

63.7

93.3

Output

Rated Output Capacity (kVA) 3

HD

6.7

9.5

12.6

17.9

ND

8

11.4

16

21.3

Rated Output Current (A)

HD

17.6

25.0

33.0

47.0

ND

21

30

42

56

Overload Tolerance

  • HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

  • ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

Note:

Derating can be necessary for applications that start and stop frequently.

Carrier Frequency

HD: 8 kHz without derating the drive capacity.

ND: 2 kHz without derating the drive capacity.

Derate the drive capacity to use values to 15 kHz maximum.

Maximum Output Voltage

Three-phase 200 V to 240 V

Note:

The maximum output voltage is proportional to the input voltage.

Maximum Output Frequency

  • V/f, OLV, OLV/PM: 590 Hz

  • AOLV/PM: 270 Hz

  • EZOLV: 120 Hz

Measures for Harmonics

DC reactor

External options

Braking Device

Braking Transistor

Standard internal characteristics

EMC Filter

EMC Filter

IEC61800-3

Factory option

Models 2xxxE: Category C3 (Conducted emission)

Power Supply

Rated Voltage/Rated Frequency

  • Three-phase AC power supply 200 V to 240 V at 50/60 Hz

  • DC power supply 270 V to 340 V

Permitted Voltage Fluctuation

-15% to +10%

Permitted Frequency Fluctuation

±5%

Input Power (kVA)

HD

8.7

11.0

17.0

24.0

ND

11

17.0

24.0

31.0

Table 4. Ratings (Three-Phase 200 V Class)

Model

2070

2082

Maximum Applicable Motor Output (kW)

HD 1

15

18.5

ND 2

18.5

22

Maximum Applicable Motor Output (HP)

HD 1

20

25

ND 2

25

30

Input

Rated Input Current (A)

HD (AC)

68

96

HD (DC)

83.3

117.6

ND (AC)

80

114

ND (DC)

98

139.6

Output

Rated Output Capacity (kVA) 3

HD

22.9

28.6

ND

26.7

31.2

Rated Output Current (A)

HD

60.0

75.0

ND

70

82

Overload Tolerance

  • HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

  • ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

Note:

Derating can be necessary for applications that start and stop frequently.

Carrier Frequency

HD: 8 kHz without derating the drive capacity.

ND: 2 kHz without derating the drive capacity.

Derate the drive capacity to use values to 15 kHz maximum.

Maximum Output Voltage

Three-phase 200 V to 240 V

Note:

The maximum output voltage is proportional to the input voltage.

Maximum Output Frequency

  • V/f, OLV, OLV/PM: 590 Hz

  • AOLV/PM: 270 Hz

  • EZOLV: 120 Hz

Measures for Harmonics

DC reactor

External options

Braking Device

Braking Transistor

Standard internal characteristics

EMC Filter

EMC Filter

IEC61800-3

Factory option

Models 2xxxE: Category C3 (Conducted emission)

Power Supply

Rated Voltage/Rated Frequency

  • Three-phase AC power supply 200 V to 240 V at 50/60 Hz

  • DC power supply 270 V to 340 V

Permitted Voltage Fluctuation

-15% to +10%

Permitted Frequency Fluctuation

±5%

Input Power (kVA)

HD

31.0

44.0

ND

37.0

52.0

1

The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output current of the drive output amps must be equal to or more than the motor rated current.

2

The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive output amps must be equal to or more than the motor rated current.

3

The rated output capacity is calculated with a rated output voltage of 220 V.