Model Specifications (Three-Phase 400 V Class)

Table 1. Ratings (Three-Phase 400 V Class)

Model

Duty Rating

4001

4002

4004

4005

4007

4009

4012

Maximum Applicable Motor Output 1 (kW)

HD

0.2

0.4

0.75

1.5

2.2

3.0

3.7

ND

0.4

0.75

1.5

2.2

3.0

3.7

5.5

Maximum Applicable Motor Output 1 (HP)

HD

1/2

3/4

2

3

3

4

5

ND

1/2

1

2

3

4

5

7.5

Input

Rated Input Current (A)

HD (AC)

1.2

1.8

3.2

4.4

6.0

8.2

10.4

HD (DC)

1.5

2.2

3.9

5.4

7.3

10

12.7

ND (AC)

1.2

2.1

4.3

5.9

8.1

9.4

14

ND (DC)

1.5

2.6

5.3

7.2

9.9

11.5

17.1

Output

Rated Output Capacity 2 (kVA)

HD

0.9

1.4

2.6

3.7

4.3

5.6

7

ND

0.9

1.6

3.1

4.1

5.4

6.8

9.1

Rated Output Current (A)

HD

1.2

1.8

3.4

4.8

5.6

7.3

9.2

ND

1.2

2.1

4.1

5.4

7.1

8.9

11.9

Overload Tolerance

  • HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

  • ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

Note:

Derating can be necessary for applications that start and stop frequently.

Carrier Frequency

HD: 8 kHz without derating the drive capacity.

ND: 2 kHz without derating the drive capacity.

Derate the drive capacity to use values to 15 kHz maximum.

Maximum Output Voltage

Three-phase 380 V to 480 V

Note:

The maximum output voltage is proportional to the input voltage.

Maximum Output Frequency

  • V/f, OLV, OLV/PM: 590 Hz

  • AOLV/PM: 270 Hz

  • EZOLV: 120 Hz

Measures for Harmonics

DC reactor

External options

Braking Device

Braking Transistor

Standard internal characteristics

EMC Filter

EMC Filter

IEC61800-3

Factory option

Models 4xxxE: Category C2 (Conducted emission)

Power Supply

Rated Voltage/Rated Frequency

Three-phase AC power supply 380 V to 480 V at 50/60 Hz

Permitted Voltage Fluctuation

-15% to +10%

Permitted Frequency Fluctuation

±5%

Input Power (kVA)

HD

1.1

1.6

2.9

4

5.5

7.5

9.5

ND

1.1

1.9

3.9

5.4

7.4

8.6

13

 
Table 2. Ratings (Three-Phase 400 V Class)

Model

Duty Rating

4018

4023

4031

4038

4044

4060

Maximum Applicable Motor Output 1 (kW)

HD

5.5

7.5

11.0

15.0

18.5

22.0

ND

7.5

11.0

15.0

18.5

22.0

30.0

Maximum Applicable Motor Output 1 (HP)

HD

10

10

15

20

25

30

ND

10

15

20

25

30

40

Input

Rated Input Current (A)

HD (AC)

15

20

29

39

50.5

59.7

HD (DC)

18.4

24.5

35.5

47.8

61.8

73.1

ND (AC)

20

24

38

44

59.7

80.7

ND (DC)

24.5

29.4

46.5

53.9

73.1

98.8

Output

Rated Output Capacity 2 (kVA)

HD

11.3

13.7

18.3

23.6

29.7

34.3

ND

13.3

17.8

23.6

29

33.5

45.7

Rated Output Current (A)

HD

14.8

18.0

24.0

31.0

39.0

45.0

ND

17.5

23.4

31.0

38.0

44.0

60

Overload Tolerance

  • HD: 150% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

  • ND: 110% of the rated output current for 60 seconds. The permitted frequency of overload is one time each 10 minutes.

Note:

Derating can be necessary for applications that start and stop frequently.

Carrier Frequency

HD: 8 kHz without derating the drive capacity.

ND: 2 kHz without derating the drive capacity.

Derate the drive capacity to use values to 15 kHz maximum.

Maximum Output Voltage

Three-phase 380 V to 480 V

Note:

The maximum output voltage is proportional to the input voltage.

Maximum Output Frequency

  • V/f, OLV, OLV/PM: 590 Hz

  • AOLV/PM: 270 Hz

  • EZOLV: 120 Hz

Measures for Harmonics

DC reactor

External options

Braking Device

Braking Transistor

Standard internal characteristics

EMC Filter

EMC Filter

IEC61800-3

Factory option

Models 4xxxE: Category C2 (Conducted emission)

Power Supply

Rated Voltage/Rated Frequency

Three-phase AC power supply 380 V to 480 V at 50/60 Hz

Permitted Voltage Fluctuation

-15% to +10%

Permitted Frequency Fluctuation

±5%

Input Power (kVA)

HD

14

18

27

36

47

55

ND

18

22

35

40

55

74

1

The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated output current of the drive output amps must be equal to or more than the motor rated current.

2

The rated output capacity is calculated with a rated output voltage of 440 V.