Installation Orientation and Spacing

Install the drive vertically for sufficient cooling airflow.

Note:

Contact Yaskawa or your nearest sales representative for details about the drive models that can be installed on its side and their operating conditions.

Figure 1. Installation Orientation
  • Upright installation
  • Horizontal installation

Single Unit Installation

Install the drive with the clearances specified in Figure 2 to guarantee sufficient space for wiring and airflow.

Figure 2. Drive Installation Space (Single Unit)
  • At least 50 mm (2 in)
  • At least 30 mm (1.2 in) on both sides
  • At least 120 mm (4.7 in) above and below
  • Airflow direction

Mounting Multiple Drives Side-by-Side

Drive models 2003xB to 2075xB and 4002xB to 4039xB can take advantage of side-by-side installation.

When installing other drive models, ensure that enough space for single unit installation is placed around each drive.

When you do side-by-side installation of drives, make sure that there is enough space for the installation of the drives with the clearances specified in Figure 3. Set L8-35 = 1 [Installation Method Selection = Side-by-Side Mounting].

Derate the output current to match the surrounding air temperature.

Figure 3. Drive Installation Space (Side-by-Side Mounting)
  • At least 50 mm (2 in)
  • At least 30 mm (1.2 in) on both sides
  • At least 2 mm (0.08 in) between each drive
  • At least 120 mm (4.7 in) above and below
Note:
  • If the dimensions of the drives are different when you do side-by-side installation, line up the tops of all the drives. This makes it easier to replace the cooling fan later.

  • Remove the top protective covers of all drives when you mount IP20/UL Type 1 drives side-by-side.

  • When you do an external heatsink installation, you cannot install drives side-by-side.

Figure 4. IP20/UL Type 1 Drives Installed Side-by-Side