Refer to Figure 1 for an example of a drive that is wired to comply with the CE Low Voltage Directive.
Figure 1. Wiring Diagram for CE Low Voltage Directive Compliance
Set L8-05 = 1 [Output Phase Loss Protect Select = Enabled] or set the wiring sequence to prevent input phase loss.
Use terminals B1, B2, -, +1, and +2 to connect options to the drive.
| Warning |
|
Fire Hazard
Only connect factory-recommended devices or circuits to drive terminals B1, B2, -, +1, and +2. Do not connect an AC power supply lines to these terminals.
Incorrect wiring can cause damage to the drive and serious injury or death from fire.
|
To protect the circuit, the main circuit is separate from the surface case that can touch the main circuit.
The control circuit is a Safety Extra-Low Voltage circuit. Use reinforced insulation to separate this circuit from other circuits. Make sure that you connect the Safety Extra-Low Voltage as specified.
Reinforced insulation separates the output terminals from other circuits. You can also connect circuits that are not Safety Extra-Low Voltage circuits when the drive output is 250 Vac 1 A maximum or 30 VDC 1 A maximum.
| Warning |
|
Electrical Shock Hazard
When you connect the shield wire of the control circuit wiring to the protective ground terminal, do not connect the protective ground wire.
If you connect the shield wire and the protective ground wire to the protective grounding terminal, it may not comply with the technical standards and local safety regulations and can cause serious injury or death.
|