Drive models BxxxA, 2xxxA, and 4xxxA must align with the conditions in this section to comply with EN 61800-3:2004/A1:2012.

Connect an EMC noise filter that complies with European standards as specified by Yaskawa to the input side (primary side). Refer to External EMC Noise Filter Selection to select the correct EMC noise filter.

Use this procedure to install an EMC noise filter to make equipment and devices added to the drive comply with the EMC Directive.

  1. Install the drive and EMC noise filter on the same grounded metal plate.
  2. Wire the drive and motor.
  3. Ground the wire shielding on the drive side and motor side.
    Figure 1. Wiring the Drive and Motor
    • Drive
    • 10 m (32.8 ft) maximum
    • Motor
    • Metal conduit
    • Grounding wire
    Note:
    • Use a braided shield cable for the drive and motor wiring or put the wires through a metal conduit.

    • Keep the wire as short as possible. The maximum wiring length between the drive and motor is:

      • BxxxA, 2xxxA, 4xxxA: 10 m (32.8 ft)

    • Keep the grounding wire as short as possible.

  4. Use a cable clamp to ground the motor cable to the metal plate.
    Note:

    Make sure that the protective ground wire complies with technical specifications or local safety standards.

    Figure 2. Ground the Shield
    • Braided shield cable
    • Metal plate
    • Cable clamp (conductive)
    Figure 3. EMC Noise Filter and Drive Installation Procedure
    • Grounding surface (Remove any paint or sealant.)
    • Enclosure panel
    • Metal plate
    • Drive
    • Ground the shield.
    • Motor
    • Motor cable (Braided shield cable: 10 m (32.8 ft) maximum)
    • Cable clamp
    • Grounding wire
    • EMC noise filter
  5. Connect the DC reactor to decrease harmonic distortion.

    Refer to DC Reactors to select a DC reactor.

    Note:
    • To comply with EN 61000-3-2 on drive models 2001 to 2006, 4001 to 4004, install a DC reactor.

    • The terminal block for the drive main circuit and the terminal block for the DC reactor have different shapes. The drive has a European-style terminal block, and the DC reactor has a round terminal block. Correctly prepare the ends of the wiring.

Ground Wiring

External EMC Noise Filter Selection

Table 1. External EMC Noise Filter (BxxxA)

Drive model

EMC Noise Filter Model

Quantity

Manufacturer

B001

FS23638-10-07

1

Schaffner

B002

FS23638-10-07

1

Schaffner

B004

FS23638-10-07

1

Schaffner

B006

FS23638-20-07

1

Schaffner

B010

FS23638-20-07

1

Schaffner

B012

FS23638-30-07

1

Schaffner

B018

FS23638-40-07

1

Schaffner

Table 2. External EMC Noise Filter (2xxxA)

Drive model

EMC Noise Filter Model

Quantity

Manufacturer

2001

FS23637-8-07

1

Schaffner

2002

FS23637-8-07

1

Schaffner

2004

FS23637-8-07

1

Schaffner

2006

FS23637-8-07

1

Schaffner

2008

FS23637-14-07

1

Schaffner

2010

FS23637-14-07

1

Schaffner

2012

FS23637-14-07

1

Schaffner

2018

FS23637-24-07

1

Schaffner

2021

FS23637-24-07

1

Schaffner

2030

FS5973-35-071

1

Schaffner

2042

FS5973-60-071

1

Schaffner

2056

FS5973-100-071

1

Schaffner

2070

FS5973-100-071

1

Schaffner

2082

RTEN-5200

1

TDK

 
Table 3. External EMC Noise Filter (4xxxA)

Drive model

EMC Noise Filter Model

Quantity

Manufacturer

4001

FS23639-5-07

1

Schaffner

4002

FS23639-5-07

1

Schaffner

4004

FS23639-5-07

1

Schaffner

4005

FS23639-10-07

1

Schaffner

4007

FS23639-10-07

1

Schaffner

4009

FS23639-10-07

1

Schaffner

4012

FS23639-15-07

1

Schaffner

4018

FS5972-35-071

1

Schaffner

4023

FS5972-35-071

1

Schaffner

4031

FS5972-60-071

1

Schaffner

4038

FS5972-60-071

1

Schaffner

4044

RTEN-5100

1

TDK

4060

RTEN-5100

1

TDK

1

When you install an external EMC noise filter, change the terminals or use the junction terminal.