Refer to Table 1 for a list of input terminals and functions.

Table 1. Multi-function Input Terminals

Type

Terminal

Name (Default)

Function (Signal Level)

Digital Inputs

S1

MFDI selection 1

(ON: Forward run OFF: Stop)

  • Photocoupler

  • 24 V, 6 mA

Note:

Install the wire jumpers between terminals SC-SP and SC-SN to set the MFDI power supply (sinking/sourcing mode or internal/external power supply).

  • Sinking Mode: Install a jumper between terminals SC and SP.

  • Sourcing Mode: Install a jumper between terminals SC and SN.

  • External power supply: No jumper necessary between terminals SC-SN and terminals SC-SP.

S2

MFDI selection 2

(ON: Reverse run OFF: Stop)

S3

MFDI selection 3

(External fault (N.O.))

S4

MFDI selection 4

(Fault reset)

S5

MFDI selection 5

(Multi-step speed reference 1)

S6

MFDI selection 6

(Multi-step speed reference 2)

S7

MFDI selection 7

(Jog command)

S8

MFDI selection 8

(Baseblock command (N.O.))

SN

MFDI power supply 0 V

MFDI power supply, 24 V (maximum 150 mA)

SC

MFDI selection common

SP

MFDI power supply +24 Vdc

Safe Disable Input

H1

Safe Disable input 1

Remove the jumper between terminals H1-HC and H2-HC to use the Safe Disable input.

  • 24 V, 6 mA

  • ON: Normal operation

  • OFF: Coasting motor

  • Internal impedance 4.7 kΩ

  • OFF Minimum OFF time of 2 ms.

H2

Safe Disable input 2

HC

Safe Disable function common

Safe Disable function common

Master Frequency Reference

RP

Master frequency reference pulse train input

(Master frequency reference)

  • Response frequency: 0 Hz to 32 kHz

  • H level duty: 30% to 70%

  • H level voltage: 3.5 V to 13.2 V

  • L level voltage: 0.0 V to 0.8 V

  • Input impedance: 3 kΩ

+V

Power supply for frequency setting

10.5 V (allowable current 20 mA maximum)

-V

Power supply for frequency setting

-10.5 V (allowable current 20 mA maximum)

A1

MFAI1

(Master frequency reference)

Voltage input or current input

Select terminal A1 with DIP switch S1-1 and H3-01 [Terminal A1 Signal Level Select].

Select terminal A2 with DIP switch S1-2 and H3-09 [Terminal A2 Signal Level Select]

  • -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)

  • 0 V to 10 V/100% (input impedance: 20 kΩ)

  • 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)

A2

MFAI2

(Combined to terminal A1)

A3

MFAI3/PTC input

(Auxiliary frequency reference)

  • Voltage input or current input

    Select using DIP switch S1-3 and H3-05 [Terminal A3 Signal Level Select].

    • -10 V to +10 V/-100% to +100% (input impedance: 20 kΩ)

    • 0 V to 10 V/100% (input impedance: 20 kΩ)

    • 4 mA to 20 mA/100%, 0 mA to 20 mA/100% (input impedance: 250 Ω)

  • PTC input (Motor Overheat Protection)

    Set DIP switch S4 to “PTC” and set DIP switch S1-3 to “V” to set terminal A3 for PTC input.

AC

Frequency reference common

0 V

E (G)

Connecting shielded cable

-